Installation Instructions
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH
4
Overview parameters
Parameters
Subcategory parameters
Description
Global
settings
Global settings
Send „in operation “(incl. cycle time), request status (active/inactive, request with…), send delay after bus voltage recovers in seconds.
CO
2
CO
2
sensor
Settings CO
2
-sensor: Enable – disable, send measured values, CO
2
offset adjustment, notification of sensor error, external value
enabled/disabled.
CO
2
control
Settings CO
2
-control: Type (inactive, 1-/2-/3-step, PI), output format, send on change / send cyclically, hysteresis (symmetrical).
Threshold 1,2,3, switching command above / below threshold, control value, blocking object
Relative
humidity
sensor
Relative humidity sensor
Settings humidity sensor: Enable – disable, send measured values, offset adjustment, notification of sensor error, external value
enabled/disabled.
Relative humidity control
Settings humidity control: Type (inactive, 1-/2-/3-step, PI), output format, send on change / send cyclically, hysteresis (symmetrical).
Threshold 1,2,3, switching command above / below threshold, control value, blocking object
Temperature
Temperature sensor
Settings temperature sensor: Enable – disable, send measured values, offset adjustment, notification of sensor error, external value
enabled/disabled.
Temperature alarms
Settings frost- and/or heat alarms: Enable – disable, send measured values.
Temperature control
Settings temperature control: Type (inactive, heating, cooling, heating & cooling), different control values (extra cooling level & guide).
Dew point
Dew point temperature
Settings dew point: Enable – disable, send measured values.
Dew point alarm
Settings dew point alarm: Enable – disable, send measured values., hysteresis (symmetrical), switching command on alarm.
Air pressure
Air pressure sensor
Settings Air pressure-Sensor: Enable – disable, send measured values, notification of sensor error, elevation.
VAV control
Settings
Settings VAV control: Enable – disable for different (already configured) PI controls, send control values according to defined parameters
and values.
Inputs
INFO
Inputs and input functions are only available in device types: GS 4x.10 / GS 3x.10 and TS 3x.10 knx.