Installation Instructions
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH
3
Application program
Manufacturer: Hugo Müller GmbH & Co KG, Sturmbühlstraße 145-149, D-78054 VS-Schwenningen
Program name: GS 4x.00 knx
Installation: Add the device to your device list and open a new project. You can download the ETS database on our webpage:
http://www.hugo-mueller.de/de/downloads/knx-produktdatenbank/
Number of communication objects:
71
Number of group adresses:
254
Number of allocations:
255
Technical Data
Power supply:
via KNX bus voltage
Bus current:
< 10 mA
Bus system:
KNX
Sensors:
CO
2
, relative humidity, temperature, dew point, VAV control
Measuring range CO
2
concentration:
390–10,000 ppm
Measuring range rel. humidity:
0–100%
Measuring range temperature:
0–50°C
Measuring range atmospheric pressure:
300-1,100 hPa
Class of protection:
IP 20 to DIN EN 60529
Permitted ambient temperature:
0°C …+50°C
Test mark:
CE
Housing:
Self-extinguishing thermoplastic
Dimensions:
80,5 x 80,5 x 17 mm
Mounting:
Wall
Type of connection:
Push-in terminal
Rights to technical amendments reserved