TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH Technical manual GS 4x.00 knx Application description – air quality sensor & control General Information The device fits for the particular use of the following tasks: monitoring of the air quality in building systems technology (schools, offices, hotels, conference venue etc.), data transfer and regulation via bus system. The device is intended for use in accordance with the defined technical data.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH Table of contents General Information ......................................................................................................................................................................................................................................................................................... 1 Application program .................................................................................................................................
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH Application program Manufacturer: Program name: Installation: Hugo Müller GmbH & Co KG, Sturmbühlstraße 145-149, D-78054 VS-Schwenningen GS 4x.00 knx Add the device to your device list and open a new project. You can download the ETS database on our webpage: http://www.hugo-mueller.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH Overview parameters Parameters Subcategory parameters Description Global settings Global settings Send „in operation “(incl. cycle time), request status (active/inactive, request with…), send delay after bus voltage recovers in seconds. CO2 CO2 sensor Settings CO2-sensor: Enable – disable, send measured values, CO2 offset adjustment, notification of sensor error, external value enabled/disabled.
TECHNICAL MANUAL GS 4x.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH Number Name Objekt size Data type 24 RFR: Control value level 3 (switching object) Object function output C - - T - 1 Bit switching 24 RFR: Control value level 3 (priority) output C - - T - 2 Bit priority switching 25 RFR: Base set point [%] input C - W - - 2 Bytes humidity (%) 26 RFR: Base set point (1 Byte) [%] input C - W - - 1 Byte percent (0...
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH Number Name Objekt size Data type 54 RTR: Control value main level heating Object function output C - - T - 1 Bit switching 55 RTR: Control value extra level heating output C - - T - 1 Byte counter pulses (0...255) 55 RTR: Control value extra level heating output C - - T - 1 Byte percent (0...
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH Communication flags Flag C R W T U Name Communication Read Write Transmit Update Meaning Object can communicate Object status can be requested (ETS, display etc.) Object can receive information Object can send information Object can request a value from another bus participant. The answer is interpreted as write command and updates the value of the communication object. This is typically used to request external sensor data after a bus voltage recovery.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH 1. Global Settings (Picture shows modified parameters) Designation Send in operation Options Inactive Sends „0“ Sends „1“ Description No function. „In operation“ (0 or 1) will be send in the configured cycle time (see next parameter).
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH 2. CO2 Sensor Designation CO2 Sensor Options Inactive Active Error CO2 sensor Send CO2 value when changing Send CO2 value cyclically Value offset -500 to +500 ppm External value Inactive Active Percentage: notify don’t notify Inactive If change above 10 – 500 ppm Inactive Every minute – once a day With xx% proportion Description CO2 sensor disabled.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH 3.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH 3.1 Switching commands / priority CO2 – Thresholds 1 / 2 / 3 Designation CO2 threshold 1/2/3 Options 400 to 1500 ppm Description Definition of threshold 1, 2 or 3 for the CO2 value. Switching command below threshold 1/2/3 off on Definition of the switching command below threshold 1/2/3. Switching command above threshold 1/2/3 off on Definition of the switching command above threshold 1/2/3.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH 3.2 PI-control for CO2 Designation Set point Options 400 to 2000 ppm Description Definition of the setpoint. Proportional band 100 to 2000 ppm Definition of the proportional band. Reset time (15…240 min.) 15 to 240 Min. Definition of the reset time. Min. control value 0% to 95% Definition of the minimal control value. The control value is limited to this minimum value. Max. control value 5% to 100% Definition of the maximum control value.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH 4. Relative humidity sensor Designation Relative humidity sensor Options Inactive Active Error humidity sensor Send relative humidity when changing Send relative humidity cyclically Value offset External value notify don’t notify Disabled If change above 1% – 25% Disabled Every minute – once a day -5% to +5% ppm Inactive Active Percentage: With xx% proportion Description Relative humidity sensor disabled.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH 5.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH 5.1 Switching commands and priority relative humidity control – Threshold 1 / 2 / 3 Designation rF threshold 1/2/3 Switching command below threshold 1/2/3 Options 20% to 50% Description Definition of threshold 1, 2 or 3 for the relative humidity value. off on If measured value is below threshold 1/2/3, switching command will not be send. If measured value is below threshold 1/2/3, switching command will be send.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH 5.2 PI control for relative humidity Designation Set point Options 10% to 95% relative humidity Description Definition of the setpoint. Proportional band 10% to 40% relative humidity Definition of the proportional band. Reset time 15 to 240 min. Definition of the reset time. Min. control value 0% to 95% Definition of the minimal control value. The control value is limited to this minimum value. Max.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH 6. Temperature Sensor Designation Temperature Sensor Options Disabled Enabled Description Temperature sensor disabled.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH 7. Temperature Alarme Designation Frost alarm Options Disabled Enabled Frost alarm when temperature Send frost alarm when change of status Send frost alarm cyclically Heat alarm < 1 °C to < 10 °C Description No function. If the alarm function is activated an alarm in the form of an object is sent when the temperature falls below a defined temperature threshold for frost alarm. When falling below the defined temperature the object frost alarm is sent.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH 8. Temperature control 8.1 Temperature control – heating and cooling PI control: A PI control is a constant control that comprises a proportional part (P-part) and an integral share (I-share). The size of the P-part is indicated in Kelvin, the I-share in minutes. At a constant PI control, the manipulated variables are operated in proportional steps up to a maximum value.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH 8.2 Temperature control – General Designation Blocking object heating mode: enable Blocking object cooling mode: enable Options Disabled Description Blocking object disabled. Enabled If the blocking object is activated, the reception of an external object can prevent the sending of the manipulated variable. Thereby an undesirable starting of actors can be prevented (e.g. do not heat if a window is open). Blocking object disabled.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH 8.3 Temperature control – Set points Designation Comfort temperature Setback of standby heating and increment of standby cooling Setback of eco heating and increment of eco cooling Interval to main level heating and cooling Options 18° to 30°C 0 K to 10 K In 0,1 °C Steps In 0,1 K Steps Description Definition of the comfort temperature. Definition of the difference to the comfort temperature in Kelvin.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH 8.4 Temperature control – Main level and extra level heating / cooling (Picture shows main level heating, PI control with output: PWM) Designation Control type Options PI control Description Selection of control type. Proportional band Reset time Control value output format PWM cycle Min.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH 9. Dew point Temperature Designation Dew point sensor Send dew point temperature when changing Send dew point temperature cyclically Options Disabled Enabled Disabled If change above … Disabled 0,1 K bis 10 K jede Minute - einmal am Tag Description No function. Sending of the recent condition. No function. If there is a change the recent control value is sent. No function. Cyclic sending of the recent control value.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH 10. Dew point Alarm Designation Dew point alarm Options Disabled Enabled Dew point alarm advance Dew point alarm hysteresis (symmetrical) Send dew point alarm when change of status Send dew point alarm cyclically Type of telegram for dew point alarm Without 1K to 5K Without hysteresis Hysteresis value when dew point alarm value at the end of dew point alarm Description No function.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH 11. Air pressure sensor Designation Air pressure sensor Options Disabled Enabled Description Temperature sensor disabled. Error air pressure Sensor Send absolute air pressure when changing Send absolute air pressure cyclically Send relative air pressure when changing Send relative air pressure cyclically Height [m. a. s. l.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH 12. VAV control Function of the VAV control: The highest value of all activated PI controls of the values from CO2, relative humidity and temperature is sent in one object.
TECHNICAL MANUAL GS 4x.00 KNX – ENGLISH 13. Inputs Inputs and input functions are only available in device types: GS 4x.10 / GS 3x.10 and TS 3x.10 knx.