Installation Instructions
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH
7
Number Name Object function C R
W T U Objekt size Data type
54
RTR: Control value main level heating
output
C
-
-
T
-
1 Bit
switching
55 RTR: Control value extra level heating output C - - T - 1 Byte counter pulses (0...255)
55 RTR: Control value extra level heating output C - - T - 1 Byte percent (0...100%)
55 RTR: Control value extra level heating output C - - T - 1 Bit switching
55 RTR: Control value extra level heating output C - - T - 1 Bit switching
56 RTR: Control value main level cooling output C - - T - 1 Byte counter pulses (0...255)
56 RTR: Control value main level cooling output C - - T - 1 Byte percent (0...100%)
56 RTR: Control value main level cooling output C - - T - 1 Bit switching
56 RTR: Control value main level cooling output C - - T - 1 Bit switching
57 RTR: Control value extra level cooling output C - - T - 1 Byte counter pulses (0...255)
57 RTR: Control value extra level cooling output C - - T - 1 Byte percent (0...100%)
57 RTR: Control value extra level cooling output C - - T - 1 Bit switching
57 RTR: Control value extra level cooling output C - - T - 1 Bit switching
58 RTR: Guide value [°C] input C - W - - 2 Bytes float value, Temperature (°C)
59 RTR: Blocking object heating input C - W - - 1 Bit enable
60 RTR: Blocking object cooling input C - W - - 1 Bit enable
61 RTR: Blocking object extra level heating input C - W - - 1 Bit enable
62 RTR: Blocking object extra level cooling input C - W - - 1 Bit enable
63 DEWP: Dew point temperature [°C] output C - - T - 2 Bytes float value, Temperature (°C)
64 DEWP: Dew point alarm enabled (switching object) output C - - T - 1 Bit switching
64
DEWP: Dew point alarm enabled (priority)
output
C
-
-
T
-
2 Bit
priority switching
64 DEWP: Dew point alarm enabled (0...100%) output C - - T - 1 Byte percent (0...100%)
64 DEWP: Dew point alarm enabled (0...255) output C - - T - 1 Byte counter pulses (0...255)
64
DEWP: Dew point alarm enabled Scene (1...64)
output
C
-
-
T
-
1 Byte
Scenen Nummer
65 DEWP: Request dew point temperature input C - W - - 1 Bit trigger
66 P: Air pressure absolute [Pa] output C - - T - 2 Bytes 2-Byte float value, Druck (Pa)
67 P: Air pressure relative [Pa] output C - - T - 2 Bytes 2-Byte float value, Druck (Pa)
68 P: Air pressure sensor error output C - - T - 1 Bit Boolean
69 P: Request absolute air pressure input C - W - - 1 Bit trigger
70 P: Request relative air pressure input C - W - - 1 Bit trigger
71 VAVR: Control value (0...255) output C - - T - 1 Byte counter pulses (0...255)
71 VAVR: Control value (0...100%) output C - - T - 1 Byte percent (0...100%)
81 E1 switching sensor output C - - T - 1 Bit switching
81 E1 Alarm sensor output C - - T - 1 Bit 1-Bit, Alarm
81 E1 switching output C - - T - 1 Bit switching