Installation Instructions

TECHNICAL MANUAL GS 4x.10 KNX ENGLISH
51
13.2.2 Function analogue input (Only available at input E1)
13.2.2.1 E1 Voltage
Designation
Options
Description
Sensor type
0-10 V
1-10 V
Selection of the connected input signal type (0-10V oder 1-10V). Also defines the
effective range.
Lower measuring limit in % of
effective range
0…100%
Lower measuring range limit.
If signal is below this value, output of „1” on object „E1 out of range”.
Upper measuring limit in % of
effective range
0…100%
Upper measuring range limit.
If signal is above this value, output of „1” on object „E1 out of range“.
Output value
1-Byte
2-Byte
4-Byte
Selection of output value type for lower / upper measuring limit.
Output value tob e sent at lower
measuring limit
Range depending on selected data type.
Definition of output value to be sent at lower measuring limit.
Output value tob e sent at upper
measuring limit
Range depending on selected data type.
Definition of output value to be sent at upper measuring limit.