Installation Instructions

TECHNICAL MANUAL GS 4x.10 KNX ENGLISH
5
Communication objects
Number
Name
Object function
C
R
W
T
U
Objekt size
Data type
1 Send ‘0’ in operation output C - - T - 1 Bit Boolean
1 Send ‘1’ in operation output C - - T - 1 Bit Boolean
2 Request status input C - W - - 1 Bit switching
3 CO2: CO2 value [ppm] output C - - T - 2 Bytes float value, pieces/million (ppm)
4 CO2: CO2 value external [ppm] input C - W - - 2 Bytes float value, pieces/million (ppm)
5 CO2: request CO2 value input C - W - - 1 Bit trigger
6 CO2: sensor error output C - - T - 1 Bit Boolean
7 CO2R: Control value (0...255) output C - - T - 1 Byte counter pulses (0...255)
7 CO2R: Control value (0...100%) output C - - T - 1 Byte percent (0...100%)
7 CO2R: Scene (1…64) output C - - T - 1 Byte Scenen Nummer
8
CO2R: Control value level 1 (switching object)
output
C
-
-
T
-
1 Bit
switching
8 CO2R: Control value level 1 (priority) output C - - T - 2 Bit priority switching
9 CO2R: Control value level 2 (switching object) output C - - T - 1 Bit switching
9
CO2R: Control value level 2 (priority)
output
C
-
-
T
-
2 Bit
priority switching
10 CO2R: Control value level 3 (switching object) output C - - T - 1 Bit switching
10 CO2R: Control value level 3 (priority) output C - - T - 2 Bit priority switching
11 CO2R: Base set point [ppm] input C - W - - 2 Bytes float value, pieces/million (ppm)
12 CO2R: Blocking object threshold 1 input C - W - - 1 Bit enable
13 CO2R: Blocking object threshold 2 input C - W - - 1 Bit enable
14 CO2R: Blocking object threshold 3 input C - W - - 1 Bit enable
15 CO2R: Blocking object input C - W - - 1 Bit enable
15 CO2R: Blocking object input C - W - - 1 Bit enable
16 rF: Humidity value [%] output C - - T - 2 Bytes humidity (%)
17 rF: Humidity value (1 Byte) [%] output C - - T - 1 Byte percent (0...100%)
18 rF: Humidity value external [%] input C - W - - 2 Bytes humidity (%)
19 rF: Request humidity value input C - W - - 1 Bit trigger
20 rF: Sensor error output C - - T - 1 Bit Boolean
21 RFR: Control value (0...255) output C - - T - 1 Byte counter pulses (0...255)
21 RFR: Control value (0...100%) output C - - T - 1 Byte percent (0...100%)
21 RFR: Scene (1…64) output C - - T - 1 Byte Scenen Nummer
22
RFR: Control value level 1 (switching object)
output
C
-
-
T
-
1 Bit
switching
22 RFR: Control value level 1 (priority) output C - - T - 2 Bit priority switching
23 RFR: Control value level 2 (switching object) output C - - T - 1 Bit switching
23
RFR: Control value level 2 (priority)
output
C
-
-
T
-
2 Bit
priority switching