Installation Instructions

TECHNICAL MANUAL GS 4x.10 KNX ENGLISH
49
13.2.1.8 Pulse counter
Designation
Options
Description
Data type
(main counter)
1-Byte value
2-Byte value
4-Byte value
Selection of data type to be used.
Limit value 1
Range depending on selected data type.
Limit value 2
Range depending on selected data type.
Counting type
Only in case of rising edge
Only in case of falling edge
In case of both edges
Only count on rising edge.
Only count on falling edge.
Count on rising as well as on falling edge.
Number of input pulses for
a counting pulse
1…10000
Number of input pulses, before increasing the count. Example: If 4 is configured, only
after 4 impulses at input, the counter changes (increases).
Counter reading change per
counting pulse
-10000…10000
Amount to increase counter after receiving before configured number of impulses. E.g. if
5 is configured, counter will increase in steps of 5.
Send counter reading at download,
ETS reset and
bus voltage recovery
Inactive
Active
Function disabled.
If active, the last counter reading after restart of the device oder after ETS reset will be
send.
Send counter reading
at change
Inactive
Active
Function disabled.
Counter reading will be sent on change.
Send counter reading
cyclically
Inactive
Active
Function disabled.
Send counter reading every seconds / …minutes / …hours.
Save counter reading
Inactive
Active
Reset counter reading at
download
Inactive
Active
Function disabled. Counter reading will be reset after a device restart.
Counter reading will be stored and stays available after restart.
Counter reading will be stored and stays available after ETS download.
Counter reading will be reset after ETS download.
Activate minimum
signal duration
Inactive
Active
At contact opening
At contact closing
Function disabled.
1…65535 x 0,1 seconds.
1…65535 x 0,1 seconds.
Debouncing time
10 to 150 ms
Definition of debouncing time for the input.
Enable object
„disable“
Inactive
Active
Communication object (blocking object) for input is disabled.
Communication object (blocking object) for input is enabled.