Designation
Options
Description
Switching /
alarm sensor
Switch
Alarm
Communication object type DPT 1.001
Communication object type DPT 1.005
Differentiation
between short
and long actuation
Inactive
Activate minimum
signal duration
Inactive
Active
Function inactive.
Definition of minimum signal duration (in 0,1s steps) for open / close.
Query input after download,
ETS reset and
bus voltage recovery
Inactive
Active
Function inactive.
Input status will be checked after a reboot of the device. A delay (in seconds) before the check can be
configured.
Active
Long actuation from
… s
0,3 to
10,0 sec.
If active, definition of when to count the actuation as a „long actuation“ can be done.
Input is being
actuated
Closed
Opened
Definition of function of input either as NO or NC contact.
Enable object
„start event 0/1“
Inactive
Active
No function.
If active, additional object (start event 0/1) is made available, which can emulate e.g. an actuation from
external and triggers event (0/1).
Reaction in case
of event 0
On / no alarm
Off / Alarm
Switchover
Inactive
Cycle off
Action on event 0 = ON
Action on event 0 = OFF
Action on event 0 = SWITCHOVER
Function disabled.
Action on event 0 = CYCLE OFF
Reaction in case
of event 1
On / no alarm
Off / Alarm
Switchover
Inactive
Cycle off
Action on event 0 = ON
Action on event 0 = OFF
Action on event 0 = SWITCHOVER
Function disabled.
Action on event 0 = CYCLE OFF
Cyclical
sending
Inactive
Active
Telegramm repeated
every … s.
1 to 65535
In seconds
No cyclical sending.
Cyclical sending according to the defined parameters (see left column).
At object value:
On
Off
On / Off
Setting, under what conditions a cyclical sending shall be performed.
Debouncing time…
in ms
10 to
150 ms
Definition of debouncing time for the input.
Enable object
„disable“
Inactive
Active
Communication object (blocking object) for input is disabled.
Communication object (blocking object) for input is enabled.