Data Sheet

PRODUCT
S
Pa
g
e 2 / 2
KNX ROOM CLIMATE CONTROLS
Air quality sensors & controls GS 4x.10 knx
Technical data
Supply voltage via KNX bus voltage
Bus current < 10 mA
Bus system KNX
Sensors
CO
Temperature
Relative humidity
Atmospheric pressure
Dew point
Manual operation
(only GS 41.10 knx)
manual adjustment of set-point temperature
(adjustment range ± 3° C, increment 0,5°)
Measuring range CO -concentration 390-10.000 ppm
Measuring range temperature 0°...+50° C
Measuring range
relative humidity
0...100%
Measuring range
atmospheric pressure
300-1.100 hPa
Permitted ambient temperature 0°...+50° C
Housing self-extinguishing thermoplastic
Housing color studio white (similar to RAL 9016)
Mounting
Wall mounting
(preferrably combined with hollow-wall box)
Type of connection
(KNX)
PCB push-in terminal block
Type of protection IP 20 (DIN EN 60529)
Class of protection III when installed according to regulations
Type of connection
external inputs
Wire diameter max. 6 x 0,5 mm²
strip length 7 mm
Functions and data provided to KNX bus:
CO
Value output
Control (step and PI control)
Relative humidity
Value output
Control (step and PI control)
Temperature
Value output
Control heating (2-point- and PI control)
Control cooling (2-point- and PI control)
Alarms
Dewpoint
Value output
Alarms
Air pressure Value output
VAV control Value output (0...100%)
and much more...
Technische Änderungen vorbehalten.
2
2
2
Hugo Müller Gmbh & Co KG | Sturmbühlstraße 145-149 | D-78054 VS-Schwenningen
Tel: +49 (0) 7720 80 836 | Fax: +49 (0) 7720 31 083 | E-Mail: info@hugo-mueller.de | Internet: www.hugo-mueller.de