Datasheet

Hugo Müller GmbH & CO KG Karlstraße 90 78054 VS-Schwenningen E-Mail: info@hugo-mueller.de www.hugo-mueller.de
BA GSxx00mod TSxx00mod Hardware HM; de, en -23876- 2023.01 V04 ED
INSTRUCTION MANUAL AIR QUALITY SENSORS GS 4X.00 MOD / GS 3X.00 MOD / TS 3X.00 MOD
SAFETY INSTRUCTIONS AND BASICS
Technical data
Safety instructions / Intended use
Power supply:
Bus current:
12-40 V DC
< 20 mA
CAUTION!
DANGER OF FIRE AND ELECTRIC SHOCK!
!!!Installation and assembly of electrical equipment must be carried out only by a skilled person!!!
Protocol / Interface
:
Modbus ASCII
,
/
RS 48
5
Connect only to suitable supply voltage [12-40 V DC].
Warranty void if housing opened by unauthorized person!
The electronic circuit is protected against a wide range of external influences. Incorrect operating may occur if external influences exceed certain limits!
Installation and assembly of electrical equipment must be in accordance with national building, electrical and safety codes!
Defective devices / sensors have to be put out of service immediately!
Observe the regulations and instructions in the ZVEI/ZVEH handbook (building system technology). Especially the professional installation of the bus lines and the
professional installation and start-up of KNX devices must be observed!
The device fits for the particular use of the following tasks: monitoring of the air quality in building systems technology (schools, offices, hotels, conference venue etc.),
data transfer and regulation via bus system.
The device is intended for use in accordance with the defined technical data.
Operate the device exclusively in a dry room!
The device is not qualified for security relevant tasks such as emergency doors, fire protection equipment, fermenting cellars etc.
Baud rates:
4800, 9600,
19200
(Default)
, 38400
Parity settings
available:
None,
e
ven
, odd
Sensors
(depending on model)
:
CO
2
, relative humidity, temperature,
atmospheric pressure
Measuring range CO2 concentration:
390
10.000 ppm
(GS
4x only)
Measuring range relative humidity
:
0
100%
(GS
4x
,
GS
3x only)
Me
asuring range temperature
:
0
50°C
Measuring range atmospheric pressure:
300
1100 hPa
absolute atmospheric pressure
(GS 4x, GS 3x only)
Analogue outputs:
3x 0
-
10V (depend
on model)
Permitted ambient temperature
:
0°…+50°C
Housing
:
self
-
ex
tinguishing thermoplastic
Mounting
:
W
all
Type of connection
:
Push
-
in connector
Type of protection
:
IP 20 to DIN EN 60529
Class of protection
:
III when installed according to regulations
The measurement results
of t
he device can be
negatively influenced by external factors. Possible
sources of interference are:
Draught and air movement:
e.g. through windows, doors, convection, heating and
people
Warming and cooling:
e.g. sunlight or mounting on an outside wall
Heat sources: close to installed electrical
consumers e.g. dimmers
Vibrations or shocks, whic
h the unites are
or were subjected to
Pollution due to colors, wallpaper paste,
dust e.g. at renovation work
Organic solvents or their vapours:
e.g. detergents
Plasticizers from stickers and packaging:
e.g. bubble wrap or polystyrene
The device is not intended for use of unauthorized
constructional alterations, repairs and security relevant
tasks
The device is not intended for use in outdoor areas and
wet rooms
The device is not qualified for security relevant tasks The
controlling of the device is only for the observation and
regulation of the air quality
The inappropriate use of the device can cause damage
to property and persons
The device has to be disposed in an environmentally
friendly manner according to the current electrical codes!
Output Measurement output
Temperature 0 50 °C (0 10 Volt)
Relative Humidity 0 100% RH (0 10 Volt)
Carbon dioxide CO
2
500 2000 ppm (0 10 Volt)
ASSEMBLY
Assembly
Disconnect device from power supply for wiring and installation purposes! Check power
supply is disconnected!
Attention! You have to check and consider the safety instructions above!
This device is suitable for wall mounting or for mounting on a flush-mounting box.
The device should not be exposed to dusty environment.
Ensure that no dust get inside of this device.
After initial startup, the device requires up to 5 minutes until the first correct measurement is possible
STEP 1:
Open the device at the bottom and remove the front cover
.
STEP 2:
Mount the rear cover to the wall or on a flush
-
mounting box
STEP 3:
Connect the RS 485 Modbus serial cable and configure device according to the project
definition.
Afterwards connect the power supply
STEP 4:
After completing the installation the front cover
must
be reattached
Installation note:
Make
sure that no wires are pinched
or squeezed when
installing the cover.
The
mounting of the device on a flush
-
mounting
box is recommended for easier
handling
and wiring
.