General technical data
Instruction manual
Mounting
www.hugo-mueller.de
CAUTION! DANGER OF FIRE AND ELECTRIC SHOCK!
!! Installation and assembly of electrical equipment must be carried out only by a skilled person !!
Ÿ Connect only to suitable supply voltage [KNX bus voltage (nominal voltage 29V)].
Ÿ Warranty void if housing opened by unauthorized person!
Ÿ The electronic circuit is protected against a wide range of external influences. Incorrect operating may occur if external in
fluences exceed certain limits!
Ÿ Installation and assembly of electrical equipment must be in accordance with national building, electrical and safety codes!
Ÿ Defective devices / sensors have to be put out of service immediately!
Ÿ Observe the regulations and instructions in the ZVEI/ZVEH handbook (building system technology). Especially the
professional installation of the bus lines and the professional installation and start-up of KNX devices must be observed!
Ÿ The device can be used in following applications: monitoring of the air quality in building systems technology
(schools, offices, hotels, conference venue etc.), data transfer and regulation via bus system.
Ÿ The device is intended for use in accordance with the defined technical data.
Ÿ The device is not qualified for security relevant tasks such as emergency doors, fire protection equipment, fermenting
cellars etc.
Ÿ The inappropriate use of the device can cause damage to property and persons.
Ÿ The device is not intended for use of unauthorized constructional alterations, repairs and security relevant tasks
Ÿ The device is not intended for use in outdoor areas and wet rooms
Ÿ The device has to be disposed in an environmentally friendly manner according to the current electrical codes!
!
Safety instructions / Intended use and inappropriate use / Disposal
Supply voltage
Bus current
Bus system
Permitted ambient
temperature
Housing
Housing color
Mounting
Type of connection
Type of protection
Class of protection
via KNX bus voltage
< 10 mA
KNX
0 ... 50 °C
self-extinguishing thermoplastic
studio white (similar to RAL 9016)
specific colors on request
wall mounting
in frame (55x55) with mounting plate
wall mounting with mounting angle
push-in connector
according to DIN EN 60529:
IP X1
IP X4 when mounted with mounting angle
III when installed according to regulations
Product specific technical data
Sensors
Source of interference
The sensor values of the device can be negatively influenced by
external impacts as e.g.:
Ÿ Draught and air movement: e.g. through windows, doors,
convection, heating and people
Ÿ Warming and cooling:
e.g. sunlight or mounting on an outside wall
Ÿ Heat sources: close to installed electrical consumers
e.g. dimmers
Ÿ Vibrations or shocks, which the unites are or were subjected to
Ÿ Pollution due to colors, wallpaper paste, dust
e.g. at renovation work
Ÿ Organic solvents or their vapours: e.g. detergents
Ÿ Plasticizers from stickers and packaging
e.g. bubble wrap or polystyrene
TS 10.00 knx
GS 10.00 knx
GS 20.00 knx
en
Fresh air calibration (GS 20.00 knx)
After initial startup, the device requires
several minutes until the sensor
sends the first values. At that time, the
lead of fresh air is recommended.
To ensure the accuracy of the VOC
sensor it´s recommended to expose the
device to fresh air very 2nd day.
The fresh air calibration can be started
via ETS object or manually by pressing
the KNX-programming button for 5 sec.
VOC (measuring range: 0...5.000 µg/m³)
relative humidity (measuring range: 0...100 %)
temperature (measuring range: 0...+50 °C)
atmospheric pressure (measuring range: 300...1.100 hPa)
dew point
VAV ventilation control
GS 10.00 knx
relative humidity (measuring range: 0...100 %)
temperature (measuring range: 0...+50 °C)
atmospheric pressure (measuring range: 300...1.100 hPa)
dew point
VAV ventilation control
TS 10.00 knx
temperature (measuring range: 0...+50 °C)
GS 20.00 knx
Step 1
Step 2
Step 3
Step 4
KNX-programming button /
Phys. adress
To disconnect the wires, push
in the front area of the
push-in connector!
!
KNX
Status LED
Disconnect the device from power supply for wiring and
installation purposes! Check power supply is disconnected!
Attention! You have to check and consider the
safety instructions above!
When using a flush-mounting box, the use of air-tight boxes
is recommended.
!
BA TS10 GS10 GS20 knx Hardware HM; de, en -24130- 2020.05V01
Hugo Müller GmbH & Co KG, Karlstraße 90, DE-78054 VS-Schwenningen
Step 1:
Step 2:
Step 3:
Step 4:
Wall mounting (standard):
Open the device by gently pulling out the rear part.
Fix the rear part directly to the wall.
After wiring and voltage recovery, press the
„programming button" to set the device into
programming mode.
(this can be done at a later time as well)
Reattach the front part.
Level
Hygienic
rating
Concentration
[µg/m³]
Recommendation
1
2
3
4
5
< 300
300 - 1.000
1.000 - 3.000
3.000 - 10.000
10.000 - 25.000
uncritical
still uncritical
remarkable
critical
unacceptable
target value
ventilation
recommended
intensified ventilation
recommended
intensified ventilation
necessary
intense ventilation
necessary
Source:
Bundesgesundheitsblatt – Gesundheitsforschung Gesundheitsschutz 2007,
50:990–1005, Springer Medizin Verlag 2007.
(DOI 10.1007/s00103-007-0290-y)
TVOC assessment (GS 20.00 knx)