Data Sheet

CONNECT - KNX
Page 2 / 2
CLIMATE CONTROLS
Particulate matter sensor GS 70.00 knx
Technical data
EAN GS 70.00 knx 4022709240750
Supply voltage via KNX bus voltage
Bus current
w/o auxiliary voltage
max. 25 mA (min. 25 V)
Bus current
with auxiliary voltage
9...12 V DC
< 5 mA
Bus system KNX
Sensors
particulate matter
VOC
temperature
relative humidity
atmospheric pressure
dew point
VAV ventilation control
Measuring range particulate matter 0...50 µg/m³
Measuring range VOC 0...5.000 µg/m³
Measuring range temperature 0...+50 °C
Measuring range
relative humidity
0...100 %
Measuring range
atmospheric pressure
300...1.100 hPa
Permitted ambient temperature 0...+50 °C
Housing self-extinguishing thermoplastic
Dimensions 80,5 x 80,5 x 17 mm
Housing color
studio white (similar to RAL 9016)
specific colors on request
Mounting
wall mounting
(preferrably combined with flush-mounting
box)
Type of connection push-in connector
Type of protection IP 20 (DIN EN 60529)
Class of protection III when installed according to regulations
Functions and data provided to KNX bus:
Particulate matter
Value output
Control (step and PI control)
Comperator
VOC
Value output
Control (step and PI control)
Relative humidity
Value output
Control (step and PI control)
Comperator
Temperature
Value output
Control heating (2-point- and PI control)
Control cooling (2-point- and PI control)
Alarms
Dewpoint
Value output
Alarms
Air pressure Value output
VAV control Value output (0...100%)
and much more...
Rights to technical amendments reserved / Technische Änderungen vorbehalten
Droits de modifications techniques réservés / Suscettibile di errori e modifiche
Hugo Müller Gmbh & Co KG | Karlstraße 90 | D-78054 VS-Schwenningen
Tel: +49 (0) 7720 80 836 | Fax: +49 (0) 7720 80 83 88 | E-Mail: info@hugo-mueller.de | Internet: www.hugo-mueller.de