INSTRUCTION MANUAL AIR QUALITY SENSORS GS 4X.00 MOD / GS 3X.00 MOD / TS 3X.00 MOD
SAFETY INSTRUCTIONS AND BASICS
Technical data
Safety instructions / Intended use
Power supply:
Bus current:
12-40 V DC
< 20 mA
CAUTION! DANGER OF FIRE AND ELECTRIC SHOCK!
!!!Installation and assembly of electrical equipment must be carried out only by a skilled person!!!
Protocol / Interface:
Modbus ASCII, Modbus RTU / RS 485
Connect only to suitable supply voltage [12-40 V DC].
Warranty void if housing opened by unauthorized person!
The electronic circuit is protected against a wide range of external influences. Incorrect operating may occur if external in fluences exceed certain limits!
Installation and assembly of electrical equipment must be in accordance with national building, electrical and safety codes!
Defective devices / sensors have to be put out of service immediately!
Observe the regulations and instructions in the ZVEI/ZVEH handbook (building system technology). Especially the professional installation of the bus lines and the professional
installation and start-up of KNX devices must be observed!
The device fits for the particular use of the following tasks: monitoring of the air quality in building systems technology (schools, offices, hotels, conference venue etc.), data
transfer and regulation via bus system.
The device is intended for use in accordance with the defined technical data.
Operate the device exclusively in a dry room!
The device is not qualified for security relevant tasks such as emergency doors, fire protection equipment, fermenting cellar s etc.
Baud rates:
4800, 9600, 19200 (Default), 38400
Parity settings available:
None, even, odd
Sensors (depending on model):
CO
2
, relative humidity, temperature,
atmospheric pressure
Measuring range CO2 concentration:
390–10.000 ppm (GS4x only)
Measuring range relative humidity:
0–100% (GS4x, GS3x only)
Measuring range temperature:
0–50°C
Measuring range atmospheric pressure:
300 – 1100 hPa absolute atmospheric pressure
(GS 4x, GS 3x only)
Analogue outputs:
3x 0-10V (depend on model)
Permitted ambient temperature :
0°…+50°C
Housing:
self-extinguishing thermoplastic
Mounting:
Wall
Type of connection :
Push-in connector
Type of protection :
IP 20 to DIN EN 60529
Class of protection:
III when installed according to regulations
Source of interference
Inappropriate use / disposal
Device configuration (example)
Analogue Outputs (depending on model)
The measurement results of the device can be
negatively influenced by external factors. Possible
sources of interference are:
■ Draught and air movement:
e.g. through windows, doors, convection, heating and
people
■ Warming and cooling:
e.g. sunlight or mounting on an outside wall
■ Heat sources: close to installed electrical consumers
e.g. dimmers
■ Vibrations or shocks, which the unites are or
were subjected to
■ Pollution due to colors, wallpaper paste, dust
e.g. at renovation work
■ Organic solvents or their vapours:
e.g. detergents
■ Plasticizers from stickers and packaging:
e.g. bubble wrap or polystyrene
The device is not intended for use of unauthorized
constructional alterations, repairs and security relevant tasks
The device is not intended for use in outdoor areas and
wet rooms
The device is not qualified for security relevant tasks The
controlling of the device is only for the observation and
regulation of the air quality
The inappropriate use of the device can cause damage to
property and persons
The device has to be disposed in an environmentally
friendly manner according to the current electrical codes!
Output
Measurement output
Temperature
0 – 50 °C (0 – 10 Volt)
Relative Humidity
0 – 100% RH (0 – 10 Volt)
Carbon dioxide CO
2
500 – 2000 ppm (0 – 10 Volt)
ASSEMBLY
Assembly
Disconnect device from power supply for wiring and installation purposes! Check power
supply is disconnected!
Attention! You have to check and consider the safety instructions above!
This device is suitable for wall mounting or for mounting on a flush-mounting box.
The device should not be exposed to dusty environment.
Ensure that no dust get inside of this device.
After initial startup, the device requires up to 5 minutes until the first correct measurement is possible
STEP 1: Open the device at the bottom and remove the front cover.
STEP 2: Mount the rear cover to the wall or on a flush-mounting box
STEP 3: Connect the RS 485 Modbus serial cable and configure device according to the project definition.
Afterwards connect the power supply
STEP 4: After completing the installation the front cover must be reattached
Installation note: Make sure that no wires are pinched or squeezed when installing the cover. The mounting of the device on a flush-mounting box is recommended for easier handling and wiring.
Power / Status LED: Green: In operation / Power on
Flashing green: False / faulty configuration (DIP-switches)
Red: Active bus communication