SPECIFICATIONS PC125-A PC125-A2 PC125-B PC125-C PC125-D PC125-F
Approvals UL UL UL UL UL UL
Voltage Input/Output (50/60Hz) 120V~ 120V~ 240V~ 120V~ 120V~ 240V~
Current Input 15A 20A 15A 30A 30A 30A
Current Output 12A 16A 12A 24A 24A 24A
Full Load VA 1440VA 1920VA 2880VA 2880VA 2880VA 5760VA
NEMA Outlets 5-15R 5-20R 6-15R 5-15R 5-20R 6-15R
Circuit Breaker 15A 20A 15/15A 15/15/30A 20/20/30A 15/15/30A
EMI/RFI Filter 20A 20A 20A 30A 30A 30A
Multi-Stage Surge Suppression 270V/150V 270V/150V 320V/270V 270V/150V 270V/150V 320V/270V
Cord/Length/Plug 14/3, 9’ 12/3, 9’ 14/3, 9’ 10/3, 15’ 10/3, 15’ 10/3, 15’
NEMA Power Input Plug 5-15P 5-20P N/A L5-30P L5-30P L6-30P
Multiple Time Delay (MTD) PC420-A PC420-A2 PC420-B PC420-C PC420-D PC420-F
RACK MOUNTED
19” x 3.4” (2U) x 8.5”.
Approximate shipping weight: 19 lbs.
(12) NEMA OUTLETS
4 unswitched and 8 switched via remote
(4) INDICATOR LIGHTS
(1) Main breaker power “ON”
(1) Power to unswitched outlets
(2) Power to switched outlets
POWER INPUT
Power cable with plug is attached to unit
through the rear panel cable grip
EMI/RFI FILTERING
Common Mode Line to Ground
Differential Mode Line to Line
SPIKE/SURGE SUPPRESSION
L-N, L-G, N-G
LOCAL/OFF/REMOTE SWITCHING
Local: Power “on or off” to the switched
outlets
Off: When breaker is “on” but this switch is
in the “off” mode, you will have power to the
unswitched outlets only
Remote: Power “on or off” to the
switched outlets via a remote device
When using a Latching remote, the
selection switch is wired for
Remote/Off/Remote - There is no
local control
OVERLOAD CIRCUIT PROTECTION
Electromagnetic breaker
provides manual on/off switching and
trips in an overload condition
(3 N/O) REMOTE I/O PORTS
Remote on/off and EPO control, EPO
overrides remote and local control
Sequence Power Up additional
equipment down line
“LT” units only: Latching remote -
(N/C) EPO, momentary start
MULTIPLE TIME DELAY(MTD)
TM
Section 1 powers on immediately
followed four seconds later by Section 2
Select PC420 in part number for MTD option
PC125-A-LT
PC125-A2-LT
PC125-B-LT
PC125-C-LT
PC125-D-LT
PC125-F-LT