Datasheet

© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999
2
SPECIFICATIONS PC125-A PC125-A2 PC125-B PC125-C PC125-D PC125-F
Approvals UL UL UL UL UL UL
Voltage Input/Output (50/60Hz) 120V~ 120V~ 240V~ 120V~ 120V~ 240V~
Current Input 15A 20A 15A 30A 30A 30A
Current Output 12A 16A 12A 24A 24A 24A
Full Load VA 1440VA 1920VA 2880VA 2880VA 2880VA 5760VA
NEMA Outlets 5-15R 5-20R 6-15R 5-15R 5-20R 6-15R
Circuit Breaker 15A 20A 15/15A 15/15/30A 20/20/30A 15/15/30A
EMI/RFI Filter 20A 20A 20A 30A 30A 30A
Multi-Stage Surge Suppression 270V/150V 270V/150V 320V/270V 270V/150V 270V/150V 320V/270V
Cord/Length/Plug 14/3, 9’ 12/3, 9’ 14/3, 9’ 10/3, 15’ 10/3, 15’ 10/3, 15’
NEMA Power Input Plug 5-15P 5-20P N/A L5-30P L5-30P L6-30P
Multiple Time Delay (MTD) PC420-A PC420-A2 PC420-B PC420-C PC420-D PC420-F
RACK MOUNTED
• 19” x 3.4” (2U) x 8.5”.
• Approximate shipping weight: 19 lbs.
(12) NEMA OUTLETS
• 4 unswitched and 8 switched via remote
(4) INDICATOR LIGHTS
• (1) Main breaker power “ON”
• (1) Power to unswitched outlets
• (2) Power to switched outlets
POWER INPUT
• Power cable with plug is attached to unit
through the rear panel cable grip
EMI/RFI FILTERING
• Common Mode Line to Ground
• Differential Mode Line to Line
SPIKE/SURGE SUPPRESSION
• L-N, L-G, N-G
LOCAL/OFF/REMOTE SWITCHING
• Local: Power “on or off” to the switched
outlets
• Off: When breaker is “on” but this switch is
in the “off” mode, you will have power to the
unswitched outlets only
• Remote: Power “on or off” to the
switched outlets via a remote device
• When using a Latching remote, the
selection switch is wired for
Remote/Off/Remote - There is no
local control
OVERLOAD CIRCUIT PROTECTION
• Electromagnetic breaker
provides manual on/off switching and
trips in an overload condition
(3 N/O) REMOTE I/O PORTS
• Remote on/off and EPO control, EPO
overrides remote and local control
• Sequence Power Up additional
equipment down line
• “LT” units only: Latching remote -
(N/C) EPO, momentary start
MULTIPLE TIME DELAY(MTD)
TM
• Section 1 powers on immediately
followed four seconds later by Section 2
• Select PC420 in part number for MTD option
PC125-A-LT
PC125-A2-LT
PC125-B-LT
PC125-C-LT
PC125-D-LT
PC125-F-LT
PC125-C Front