Technical data
64 i-KI MTD / i-KIR MTD EN 10/2010
LIST OF PARAMETERS
U I A
Description Menu Parameter no. UOM
Enable domestic hot water set point: 0 = Economy, 1 = Comfort Mn00 0015
Domestic hot water Economy set point Mn00 0022 °C
Domestic hot water Comfort set point Mn00 0023 °C
User password Mn00 0036
Enable remote contact: 0= remote contact enabled, 1= remote contact disabled (selection from keypad only) Mn01 0100
Automatic mode changeover set point in HEATING Mn01 0106 °C
Automatic mode changeover differential in HEATING Mn01 0107 °C
Automatic mode changeover set point in COOLING Mn01 0108 °C
Automatic mode changeover differential in COOLING Mn01 0109 °C
Type of outlet heater operation: 0 = Supplementary , 1 = Replacement Mn01 010G
Type of boiler operation: 0 = Supplementary , 1 = Replacement Mn01 010H
Maximum return set point limit in cooling mode (Tm1) Mn01 0128 °C
Outside minimum temperature corresponding to max. return temperature (Te1) Mn01 0129 °C
Enable compensation for room humidity, ZONE LT3: 0= Disabled , 1= Enabled Mn01 012N
Room relative humidity value to start increasing water outlet temperature set point, ZONE LT3 Mn01 012P %
Maximum outlet temperature hysteresis corresponding to 100% relative humidity Mn01 012R °C
Minimum return set point limit in cooling mode (Tm2) Mn01 0130 °C
Maximum outside temperature corresponding to min. return temperature (Te2) Mn01 0131 °C
Maximum outlet temperature set point limit in cooling mode (Tm1) Mn01 0132 °C
Minimum outside temperature corresponding to max. outlet temperature (Te1) Mn01 0133 °C
Minimum outlet temperature set point limit in cooling mode (Tm2) Mn01 0134 °C
Maximum outside temperature corresponding to min. outlet temperature (Te2) Mn01 0135 °C
Maximum outlet temperature set point limit in cooling mode (Tm1) Mn01 0136 °C
Minimum outside temperature corresponding to max. outlet temperature (Te1) Mn01 0137 °C
Minimum outlet temperature set point limit in cooling mode (Tm2) Mn01 0138 °C
Maximum outside temperature corresponding to min. outlet temperature (Te2) Mn01 0139 °C
Inside temperature to enable frost protection Mn01 0140 °C
Outside air temperature for frost protection Mn01 0141 °C
Enable SYSTEM compensation curve 0= Disabled 1= Enabled Mn01 0152
Fixed return water temperature set point in HEATING Mn01 0153 °C
Enable SYSTEM compensation curve: 0= Disabled, 1= Enabled Mn01 0154
Fixed return water temperature set point in COOLING Mn01 0155 °C
Enable compensation for room humidity, SYSTEM: 0= Disabled , 1= Enabled Mn01 0156
Room relative humidity value to start increasing SYSTEM return water set point Mn01 0157 %
Maximum return temperature hysteresis corresponding to 100% relative humidity Mn01 0158 °C
SYSTEM compensation curve number Mn01 0159
Enable contact as: 0= Alarm signal, 1= Dehumidifier, 3= Secondary circuit pump Mn01 015A
Enable compensation curve for zone LT3 0= Disabled 1= Enabled Mn01 015E
Enable room temperature influence on SYSTEM 0= Disabled 1= Enabled Mn01 0163
SYSTEM Room Authority Mn01 0164 %
Minimum set point limit for SYSTEM curve Mn01 0165 °C
Maximum set point limit for SYSTEM curve Mn01 0166 °C
Enable compensation curve for zone LT1 0= Disabled 1= Enabled Mn01 0167
Enable compensation curve for zone LT1: 0= Disabled, 1= Enabled Mn01 0169
Enable compensation for room humidity, ZONE LT1: 0= Disabled , 1= Enabled Mn01 0171
Room relative humidity value to start increasing water outlet temperature set point, ZONE LT1 Mn01 0172 %
Maximum outlet temperature hysteresis corresponding to 100% relative humidity Mn01 0173 °C
Zone LT1 compensation curve number Mn01 0174
Enable room temperature influence on LT1 0= Disabled 1= Enabled Mn01 0178
LT1 Room Authority Mn01 0179 %
MINIMUM outlet set point limit for compensation curve in zone LT1 Mn01 0180 °C
MAXIMUM outlet set point limit for compensation curve in zone LT1 Mn01 0181 °C
Enable compensation curve for zone LT2 0= Disabled 1= Enabled Mn01 0182
Enable compensation curve for zone LT2: 0= Disabled, 1= Enabled Mn01 0184
Enable compensation for room humidity, ZONE LT2: 0= Disabled , 1= Enabled Mn01 0186
Room relative humidity value to start increasing water outlet temperature set point, ZONE LT2 Mn01 0187 %
Maximum outlet temperature hysteresis corresponding to 100% relative humidity Mn01 0188 °C
Zone LT2 compensation curve number Mn01 0189
Enable room temperature influence on LT2 0= Disabled 1= Enabled Mn01 0193
LT2 Room Authority Mn01 0194 %
MINIMUM outlet set point limit for compensation curve in zone LT2 Mn01 0195 °C
MAXIMUM outlet set point limit for compensation curve in zone LT2 Mn01 0196 °C
Electric heater operating mode: 0 = heat pump only, 1 = electric heater only, 2 = heat pump + electric heater Mn02 0202
Domestic hot water set point with heater Mn02 0209 °C