MAINTENANCE AND SERVICE
A
Description
Electric heater operating mode
0 = heat pump only
1 = electric heater only
2 = heat pump + electric heater
Menu
Mn02
Parameter
no.
0202
Valore da
impostare
1
UOM
Description
Type of outlet electric heater oper-
ation
0 = Supplementary
1 = Replacement
Enable manual heater operation
Menu
Mn01
Mn06
Parameter
no.
010G
0620
Default
1
1
UOM
Set the parameters following the sequence described in
the table
SYSTEM emergency operation
If the heat pump is not working correctly or the compressor
has shut down, emergency operation can be activated.
Emergency operation involves heating the water using the
electric heaters available on the system (outlet, storage
tank).
The compressor remains off.
To enable manual operation of system heaters, set parame-
ter 0620 = 1 (manual)
DOMESTIC HOT WATER emergency operation
If the heat pump is not working correctly or the compressor
has shut down, emergency operation can be activated.
Emergency operation involves heating the domestic hot
water using the electric heater inside the storage tank.
To enable manual operation of DHW storage heaters, set
parameter 0202 = 1
SHUTTING DOWN FOR LONG PERIODS
A
After deactivating the heat pump:
- Disconnect the unit from the power supply.
- Make sure the remote keypad is in the “OFF” position.
- Place QF1 in the OFF position (see wiring diagram).
- Deactivate the indoor terminal units by placing the switch
of each unit in the “OFF” position.
- Close the water valves.
If the outside temperature may fall below zero; there is
the risk of freezing.
The water circuit MUST BE EMPTIED AND CLOSED (if
draining after operation in heat pump mode, beware that
the water may be hot), or antifreeze must be added in
the proportion recommended by the manufacturer.
It is recommended to use non-toxic food grade
antifreeze, compliant with the standards in force in the
countries where the unit is used, if domestic hot water
production is also featured.
If the mains switch is turned to “off” for more than four
hours, after turning it on and before reactivating the unit,
leave the power on but the unit deactivated for at least
two hours to preheat the oil in the compressor sump.
Resetting alarms displayed by the board on the unit
Press the PUMP SW and RESET SW buttons at the same
time for 5 seconds to reset the alarm.
The alarms are reset automatically no operations are carried
out for 5 minutes.
While an error code is being displayed, holding the reset
button for 10 seconds or more resets the alarm log.
Alarm log shown by the board on the unit
Press and hold the PUMP SW and RESET SW buttons
together for 5 seconds until the log of error codes and the
sequential number is shown.
The PUMP SW button is used to select a maximum of 8
past error codes on the display.
If there are no errors saved, the display shows "--".
RESET SW
alarm no.
PUMP SW
0031m
0011m