Technical data

61EN 10/2010 i-KI MTD / i-KIR MTD
MAINTENANCE AND SERVICE
I A
ERROR
CODE
FEATURES, PARTS, COMPONENTS
MALFUNCTIONING
CHECKS SOLUTION SIZE
P1
Circulating pump
error
CIRCULATING PUMP PRINTED
CIRCUIT BOARD (PCB) (*1)
Check pump voltage
If the voltage is within the standard values, the pump does
not need to be replaced. If the voltage is not within the
standard values, replace the printed circuit board (PCB).
0011-0031
WATER PUMP BLOCKED
WATER CIRCUIT BLOCKED
Check the pump and the water cir-
cuit.
Remove any obstructions, clean the water filter, unblock the
pump.
P3
High pressure
switch error
High pressure switch
Check loose cable connections and
contacts
if the same error appears again replace the
high pressure
switch
0061
U5
Below-normal tem-
perature measured
THE OUTSIDE TEMPERATURE
FALLS BELOW -20°C
The unit should not be operated
below -20°C to protect the various
components
When the temperature increases again, the unit automati-
cally resumes operation
0031
OUTSIDE TEMPERATURE PROBE
Check resistance using a tester
[see table 1]
Replace the probe if faulty
No cooling
No heating
4-WAY VALVE Check resistance using a tester If the value is not within the standard range, replace the coil
0011-0031
OUTSIDE AIR RECIRCULATION
Check air blockages at intake and
outlet
Make sure the position doesn’t block the air intake and out-
let
WATER CIRCULATION OUTLET
AND RETURN TEMPERATURE
PROBE
Check resistance using a tester
[see table 1]
If one of these probes is faulty, replace it
0031
Check resistance using a tester
[see table 5]
0011
GAS LEAK
Check the service valve and the
refrigerant circuit.
After having repaired the leak, collect all the refrigerant and
then recharge to the specified mass
0011-0031
WATER CIRCUIT BLOCKED
Check the temperature difference
between water outlet and return.
If the difference is high it means
that water flow-rate is too low.
Remove obstructions, clean the water filter and unblock the
pump.
ON
4
3
2
1
OFF
MODE SW.
Monitor display
PCB (DISPLAY)
RESET SW.
PUMP SW.
Table 1
Defrost temperature probe
(0031m)
Outside temperature probe
Suction temperature probe
(0031m)
Water circulation outlet
temperature probe
Table 3
Defrost temperature probe
(0011m, 0061m)
Suction temperature probe
(0011m, 0061m)
Table 2
Discharge temperature probe
(0031m)
Heat pump display
To display the data measured by the probes on the outdoor
unit, set switch 4 on the display to the ON position.
Then scroll the data shown in the table using the PUMP SW
button.
TEMPERATURE
(°C)
Resistance
(kΩ)
0 31
5 24
10 19
15 15
20 12
25 10
30 8
35 6,7
40 5,5
45 4,6
50 3,8
55 3,2
TEMPERATURE
(°C)
Resistance
(kΩ)
0 29
5 23
10 19
15 15
20 12
25 10
30 8,3
35 6,9
40 5,7
45 4,8
50 4,1
55 3,4
TEMPERATURE
(°C)
Resistance
(kΩ)
10 1000
20 600
35 300
40 250
50 160
80 50
Table 4
Discharge temperature
probeo (0011m, 0061m)
TEMPERATURE
(°C)
Resistance
(kΩ)
10 100
20 64
35 33
40 27
50 18
80 6,4
Table 5
Circuit water outlet and return
temperature probe (0011m)
Monitor Data Display Monitor Description Unit
d0 Water return temperature 1 °C
d1 Compressor operating frequency 1 Hz
d2 Discharge temperature 1 °C
d3 Power consumption 100 W
d5 Defrost thermistor temperature 1 °C
d6 Room air temperature 1 °C
d8 Suction temperature 1 °C
d9 Water outlet temperature 1 °C
TEMPERATURE
(°C)
Resistance
(kΩ)
0 31
10 19
20 12
30 8,1
40 5,5
50 3,8