Technical data

48 i-KI MTD / i-KIR MTD EN 10/2010
Maximum room humidity compensation
The water outlet temperature set point, calculated based on
the compensation curve, can be compensated according to
the maximum relative humidity in the room.
The water outlet temperature value can increase so as to
avoid possible formation of condensate in the radiant cool-
ing systems (underfloor, ceiling, wall, etc.).
If the relative humidity measured by the A5 room unit A5
exceeds the value set for parameter 012P, 0172, 0187, the
water outlet temperature set point increases until reaching
the maximum outlet temperature.
The maximum outlet temperature is the set point calculated
according to the compensation curve in cooling mode plus
the value set for parameter 0158, 0173, 0188.
Description
Enable compensation for room
humidity, SYSTEM
0= Disabled 1= Enabled
Room relative humidity value to start
increasing water outlet temperature
set point SYSTEM
Maximum outlet temperature hys-
teresis corresponding to 100% rela-
tive humidity
Enable compensation for room
humidity, ZONE LT1
0= Disabled 1= Enabled
Room relative humidity value to start
increasing water outlet temperature
set point ZONE LT1
Maximum outlet temperature hys-
teresis corresponding to 100% rela-
tive humidity
Enable compensation for room
humidity, ZONE LT2
0= Disabled 1= Enabled
Room relative humidity value to start
increasing water outlet temperature
set point ZONE LT2
Maximum outlet temperature hys-
teresis corresponding to 100% rela-
tive humidity
Enable compensation for room
humidity, ZONE LT3
0= Disabled 1= Enabled
Room relative humidity value to start
increasing water outlet temperature
set point ZONE LT2
Maximum outlet temperature hys-
teresis corresponding to 100% rela-
tive humidity
* Parameters to be set only when the heat pump is connected
directly to the system, without storage tank on the outlet.
Menu
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Parameter
no.
0156 *
0157 *
0158 *
0171
0172
0173
0186
0187
0188
012N
012P
012R
Default
0
70
15
0
70
15
0
70
15
0
70
15
UOM
%
°C
%
°C
%
°C
%
°C
CONTROL AND OPERATING CHARACTERISTIC
A
Te2 Outside temp.Te1
Tm2
Tm1
Outlet
set point
The compensation curves in COOLING are divided into:
SYSTEM curve determines the general water outlet tem-
perature to the terminal units.
• ZONE curve determines the water outlet temperature in
the mixed circuit.
For systems configured with mixed zones, the SYSTEM
curve and ZONE curve must be selected.
The system and zone curve work in cascading, the mixed
zone curve may therefore not request a higher value than
the one supplied by the system curve.
Water outlet set point compensation diagram in COOL-
ING
The compensation curve in cooling mode can be modified to
allow correct heat pump operation depending on the cooling
system used (radiant panels, fan coils).
Points T1 and T2 correspond to two outside temperature
values that respectively identify the maximum and minimum
system outlet temperature.
Description
Enable SYSTEM compensation curve
0= Disabled
1= Enabled
Maximum outlet temperature set point limit
in cooling mode (Tm1)
Minimum outside temperature corresponding
to max. outlet temperature (Te1)
Minimum outlet temperature set point limit in
cooling mode (Tm2)
Maximum outside temperature correspond-
ing to min. outlet temperature (Te2)
Enable compensation curve zone LT1
0= Disabled
1= Enabled
Maximum outlet temperature set point limit
in cooling mode (Tm1)
Minimum outside temperature correspond-
ing to max. outlet temperature (Te1)
Minimum outlet temperature set point limit in
cooling mode (Tm2)
Maximum outside temperature correspond-
ing to min. outlet temperature (Te2)
Enable compensation curve zone LT2
0= Disabled
1= Enabled
Maximum outlet temperature set point limit
in cooling mode (Tm1)
Minimum outside temperature corresponding
to max. outlet temperature (Te1)
Minimum outlet temperature set point limit in
cooling mode (Tm2)
Maximum outside temperature correspond-
ing to min. outlet temperature (Te2)
Enable compensation curve zone LT3
0= Disabled
1= Enabled
Maximum outlet temperature set point limit
in cooling mode (Tm1)
Minimum outside temperature corresponding
to max. outlet temperature (Te1)
Minimum outlet temperature set point limit in
cooling mode (Tm2)
Maximum outside temperature correspond-
ing to min. outlet temperature (Te2)
Menù
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Parameter
no.
0154
0128
0129
0130
0131
0169
0132
0133
0134
0135
0184
0136
0137
0138
0139
011T
012H
012J
012L
012M
Default
0
20
23
18
36
0
20
23
18
36
0
20
23
18
36
0
20
23
18
36
UOM
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
100% UR%Value parameter 0157
Value parameter 0172
Value parameter 0187
Room
humidity (RH%)
Value:
parameter 0158
parameter 0173
parameter 0188
Outlet
temperature
hysteresis (°C)