Technical data
44
i-KI MTD / i-KIR MTD EN 10/2010
ACCESSING THE PROGRAMMING LEVELS
The room controller has a menu structure, divided into levels so as to allow access only to authorised users, as shown below:
Procedure for accessing the menu
x3 sec.
• Main display
• Press the + buttons together for 3 sec-
onds
• Turn the knob and select the password (as
shown in the table)
1 2 3
OPERATION AND FUNCTIONS OF THE ROOM CONTROLLER
A
➔
Unit ON - ZONE ON
• Press the button for 3 seconds
Unit OFF - ZONE OFF
x3 sec.
1 2 3
Switching OFF
The button disables operation of the pump or the zone valve controlled by the room controller, the heat pump is deactivated
using the button, as shown in " Selecting the operating mode".
Level Password Menu description Menu code
User 012 Room unit Mnu00
Installer
022 Zone room terminal address setting Addr
034
System configuration Mnu01
DHW Mnu02
Supplem. sources Mnu03
Cascade/Forced fan Mnu04
Primary and DHW exchanger Mnu06
input / output Mnu09
Authorised technical service Contact Manufacturer
Compressor Mnu05
Source heat exchanger Mnu07
Defrost Mnu08
Alarm log Mnu11
Serial protocol Mnu12