Technical data

32 i-KI MTD / i-KIR MTD EN 10/2010
Outside air temperature (°C)
COOLING
Water outlet temperature (°C)
15
20
25
30
35
40
45
0 5 10 15 20 25
Outside air temperature (°C)
HEATING
Water outlet temperature (°C)
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
15 25 35 45 55 65
OPERATING LIMITS
I A
Min/max water temperature difference = 5/10 °C (in minimum flow conditions, 7 l/min)
MAX return temperature to heat pump = 55°C
MAX outlet temperature to heat pump for DHW production = 58°C
Water circuit pressure min/max = 1/3 bar
Maximum glycol percentage = 40%
The temperature of the fluid leaving the unit must always be within the manufacturer’s specified operating range, even during
start-up and when first putting into heating mode. To ensure this, the water circuit can be fitted with a bypass valve and/or other
solutions, such as electric heaters with temperature control inside the storage tank.