Technical data
21EN 10/2010 i-KI MTD / i-KIR MTD
INSTALLER CONNECTIONS TO BE PERFORMED ON THE INSIDE MODULE
A5 room controller connection
Installation instructions
The room controller must be installed in the best reference
position for temperature control.
Position the room controller as follows:
• around 1.5 metres from the floor, in a part of the room that
allows the sensor to accurately measure the room temper-
ature;
• away from cold air flows, sunlight or other sources of heat.
• leave enough space above the room controller to allow
assembly and removal where necessary.
• If the room controller is removed from its base, it discon-
nects from the power supply and consequently is no
longer operating.
min.
10 cm
Installation procedure
Assembly
• Separate the front from the rear of the terminal using a
screwdriver r (1)
• Disconnect the 4-pin connector from the front part (2)
• Remove the cover A1, unscrewing the screw A2 (3).
• Fix the controller support to the wall using the holes A3
(4). Support hole size and spacing in figure (5).
• Make the electrical connections as shown in the figure (6),
also see the wiring diagram.
A2
A1
A3
A3
E
131
83,5
86
51
52 53 54 55
TxRx -
TxRx +
GND
24 VAC
GND
A5 room controller terminal block Installer terminal block
Number of wires 5 shielded
Power supply wire size 0.5 mm
2
Maximum distance 500 m
1
3
6
4 5
2
I A