Technical data
UPS MTD-XL
Operation
MTD series
58
7. Operation
7.1 Operation of the UPS
The operator of the UPS-system must always adhere to the instructions
in this operating manual. The operator may only carry out the following
measures and must always exercise particular care:
Use of the operating controls: switching-on, starting and switching-
off the UPS.
Reading of the display messages and interpretation of the acoustic
warning signals.
Triggering the test mode.
Using the communication interface, whereby the connection to the
PC or other systems must already be established for UPS-devices
with permanent wiring.
Due to the extensive protective functions the UPS-system performs in re-
lation to the appliance/s, the UPS operates fully automatically. The opera-
tor only carries out the switching-on and starting or switching-off of the
device. In addition, a data exchange can take place via the communica-
tion interface or the SNMP-adapter, however, this is not absolutely nec-
essary for the general operation of the system.
7.1.1 UPS operating modes
Normal operating mode:
In normal operating mode the UPS operates with an input voltage of + / - 20 %.
Generator mode:
In generator mode the UPS operates with an input frequency between 40 Hz
and 70 Hz. Outside of this range, the UPS switches to battery mode.










