Technical data
UPS MTD 700 / 1000 / 1500 / 2000 / 3000
Technical Data
MTD Series
59
12.2 Device Specifications for Rack Mountable
MTD model
700RM
1000RM
1500RM
2000RM
3000RM
Power
Power in VA
700
1000
1500
2000
3000
Power in W
438
625
938
1250
1875
Bridging
period
Nominal load
4 min
3 min
2 min
4 min
3 min
Input
Nominal voltage
230 V AC
Input voltage area
170~ 300 VAC
Input frequency area
45~ 70 Hz Auto-sensing
Boost start threshold /
shut down
195.5 VAC ± 2 % / 205.5 V AC ± 2 %
Boost start threshold /
shut down
264.5 VAC ± 2 % / 254.5 V AC ± 2 %
Under-voltage warn-
ing threshold / All
clear
170 VAC ± 2 % / 180 V AC ± 2 %
Over-voltage warning
threshold / All clear
300 VAC ± 2 % / 290 VAC ± 2 %
Output
Output voltage
Can be set on the LCD display to
220, 230, 240 V AC
Voltage tolerance
Line mode ± 15 %,
Battery mode < 3 % RMS
Frequency tolerance
Line mode 50 Hz or 60 Hz,
Battery mode ± 0.1 Hz
Power factor
0.625
Voltage form
Sinusoidal
Efficiency
> 80 %
DC start
Cold start
Yes
Switching
time
Typical
< 4 msec.
Battery
Nominal voltage
24 VDC
36 VDC
Number of blocks x
Nominal capacity /
Block
4 x 6V/ 7Ah
3 x 9 Ah
6 x 7 Ah
Type
Closed, maintenance-free
VRLA batteries
Life expectancy
approx. 5 years (depending on the environmental
conditions) option for 10 years
Charging time
approx. 5 hours to 90 %