Operating instructions

TM 5-6115-584-12
NAVFAC P-8-622-12
TO 35C2-3-456-1
TM-05682C-12
OPERATING INSTRUCTIONS
BEFORE STARTING SET
1.
INSURE MAIN CIRCUIT BREAKER IS OFF.
2.
REMOVE ASK DOOR LABELED “OIL-FILL, DRAIN, FILTER”.
FILL CRANKCASE (DO NOT
OVERFILL).
FILL FUEL TANK.
ENSURE THAT VENT ON UNDERSIDE OF FUEL FILLER
CAP IS OPEN BEFORE STARTING GENERATOR SET.
3.
‘WARNING”
- GROUND SET TO AVOID SHOCK HAZARD.
LIFT FLAP ON ASK REAR PANEL
ASSEMBLY TO CHECK THAT GENERATOR SET IS PROPERLY GROUNDED.
4.
SET BATTERIES ARE NEGATIVE GROUND.
5.
INSURE ALL DOORS ARE IN PLACE, CLOSED AND LATCHED FOR OPERATION.
STARTING SET
1.
MOVE “MASTER SWITCH” TO “PRIME & RUN” POSITION TO ALLOW FUEL TO PRIME SET.
2.
MOVE “MASTER SWITCH” TO “PREHEAT” POSITION AND HOLD FOR (1) MINUTE.
NOTE:
PREHEAT IS NOT REQUIRED WHEN ENGINE IS HOT.
3.
MOVE
“MASTER SWITCH” TO “START”
POSITION AND HOLD UNTIL ENGINE FIRES
CONTINUOUSLY.
IF ENGINE DOES NOT START WITHIN 15 SECONDS, REPEAT STEPS 1
AND 2.
4.
“MASTER SWITCH” WILL RETURN TO
“PRIME & RUN” POSITION WHEN RELEASED. IF
RUNNING FROM AUXILIARY FUEL SOURCE, MOVE ‘MASTER SWITCH” TO “PRIME & RUN AUX
FUEL” POSITION.
5.
AFTER WARM UP,
CHECK FREQUENCY AND VOLTAGE AND ADJUST IF NECESSARY.
LIFT
FLAP LABELED ‘SPEED CONTROL” FOR SET FREQUENCY ADJUSTMENT.
6.
MOVE “AC CIRCUIT BREAKER” TO “ON” POSITION.
STOPPING SET
1.
MOVE “AC CIRCUIT BREAKER” TO “OFF” POSITION.
2.
MOVE “MASTER SWITCH” TO ‘OFF” POSITION.
3.
FOR EMERGENCY STOP, PULL
“DC CONTROL CIRCUIT BREAKER”.
SERVICE INSTRUCTIONS
AMBIENT
FUELS
LUBRICATING OIL
TEMPERATURE CAPACITY:
5KW-7 GAL 1OKW-12.5 GAL
CAPACITY (LESS FILTER)
5KW-3 QT
1OKW-5.5 QT
PRIMARY-DIESEL
EMERGENCY-JP4
-65° TO -25° F
VV-F-800
-54° TO -32° C
FOR JP4 OPERATION
GRADE DFA
SEE INSTRUCTION
MIL-L-10295
.
MANUAL
-25” TO -10” F
-32° TO -23” C
VV-F-800
GRADE DF1
-10°
TO +30° F
MIL-L-2104
-23° TO -1° C
GRADE
10
+30°
TO +100° F
-1°
TO +38° C
VV-F-800
GRADE DF2
MIL-L-2104
+100° TO +107° F
GRADE
30
+38°
TO
+42° C
Figure 5-1.
Instruction and Rating Plates (Sheet 1 of 4)
Change 7
5-3