TIME BANDS
The HSW11 controller can manage the unit based o the time and the day of the week.
The controller features four time bands in three profiles that can be combined, when programming, with the days of the week.
The profile defines the behaviour of the unit over a 24 hour period.
Time band management must be enabled by parameter tE00 = 1 (tE00 = 0 standard setting).
Programming example
1) Define the profile for each time band, as shown in the following table.
2) Associate one of the three programmed profiles with each day of the week.
The days of the week are identified by the parameters tE01 to tE07; tE01 = Monday, tE02= Tuesday……tE07=Sunday.
Once having displayed the day of the week, tE01 to tE07, select the value 1, 2 or 3 corresponding to Profile 1, Profile 2 and
Profile 3 respectively.
Follow the operations shown below to program the profiles and combine them with the day of the week:
Description Description Profile 1 Profile 2 Profile 3
Hour / Minutes hours 00 (tE10=0) / min.00 (tE11=0) hours 00 (tE38=0) / min.00 (tE39=0) tE66..tE67
Operating mode ON/Standby ON (tE12=0) ON (tE40=0) tE68
TIME BAND 1 Cool set point tE13=15 tE42=15 tE69
Heat set point tE14=30 tE42=30 tE70
DHW set point tE15=50 tE43=50 tE71
Hour / Minutes hours 6 (tE17=6) / min.00 (tE18=0) hours 7 (tE45=6) / min.00 (tE46=0) tE73..tE74
Operating mode ON/Standby ON (tE19=0) ON (tE47=0) tE75
TIME BAND 2 Cool set point tE20=12 tE48=12 tE76
Heat set point tE21=33 tE49=33 tE77
DHW set point tE22=45 tE50=45 tE78
Hour / Minutes hours 9 (tE24=9) / min.00 (tE25=0) hours 7 (tE52=12) / min.00 (tE53=0) tE80..tE81
Operating mode ON/Standby ON (tE26=0) ON (tE54=0) tE82
TIME BAND 3 Cool set point tE27=15 tE55=12 tE83
Heat set point tE28=30 tE56=33 tE84
DHW set point tE29=50 tE57=45 tE85
Hour / Minutes hours 17 (tE31=17) / min.00 (tE32=0) hours 17 (tE59=17) / min.00 (tE60=0) tE87..tE88
Operating mode ON/Standby ON (tE33=0) ON (tE61=0) tE89
TIME BAND 4 Cool set point tE34=12 tE62=12 tE90
Heat set point tE35=33 tE63=33 tE91
DHW set point tE36=45 tE64=45 tE92
Example of profile 1 to be used
on opening days
Example of profile 2 to be used
on closing days
To access directory tE from the main display, press esc and
set together. [esc+set].
Pressing these two buttons enters the menu with the list of
directories.
Use the up and down buttons to scroll to the directory PAr.
Press the set button and use the up and down buttons to
scroll to the directory tE.
Press the set button to display the first parameter, tE00. Use
the up and down buttons to scroll to the other parameters.
To set the selected parameter, press the set button and
enter the value using the up and down buttons.
Confirm the changes by pressing the set button or alterna-
tively cancel by pressing esc.