Specifications

PRESSURE
t
T -/
REGULATORJFILTER
l/4 INCH NPT
FEMALE
CONNECTION
SUPPLY AIR
>I00 PSIG
/i
2~~ TO PILOT
--- VALVE
SHUTOFF VALVE
VIEW A
POWER POSITIONER WITH
CURRENT TO PNEUMATIC SIGNAL
CONVERTER (l/P)
AIR
FILTER
t-----L
15 FEET
MAXIMUM
15 PSIG OR I
3-.- -.- -..
O-30 PSIG
SIGNAL AIR
PRESSURE
i/4 INCH NPT
II
FEMALE
CONNECTION
\
SUPPLY AIR
>I00 PSIG
VIEW B
POWER POSITIONER WITH
PNEUMATIC CONTROL SIGNAL
AIR $8)
3/S INCH NPT
FEMAL:
FILTER CONNECTION
Figure 2-4. Air Piping Schematic
TO
DIAPHRAGM
AIR
CONNECTION
MANIFOLD
AIR
CONNECTION
-MANIFOLD
2-5. CURRENT TO PNEUMATIC SIGNAL
CONVERTER WP) ELECTRICAL
CONNECTIONS. Connect electrical signal input to
I/P converter and calibrate if necessary. Refer to
paragraph 4-3 for calibration procedures. The
connections must be made by screw terminals. If the
I/P has pigtail leads instead of screw terminals, the
connection must be made at a tam&d block. Gage of
wire required is 18 gage signal wire. The signal that
will control the I/p should have a range of 4 to 20
mA at a voltage of 24 vdc.
IE-102-208
2-4