Verifying output signals
(11) Indicate [Inp: output port operation] by pressing the
[UP] key or [DOWN] key.
(12) To operate output ports, press the [ADJ] key at least
0.1second.
The first digit flashes. You can operate output ports.
(Re-pressing the [ADJ] key at least 0.1 second inhibits
[output port operation].
(13) Press the [UP] key to specify which output port is to
be operated.
Every pressing the key shifts the code number in the
order of the figures to the right.
(14) Press the [DOWN] key to turn ON/OFF the selected
port.
Every pressing the key turns over the port state (ON
OFFON).
(15) Check the host input state reacting to the above
operation.
J Verify the signals are received.
(16)To terminate operation of the output port, press the
[SET] key at least 0.1 second.
Flashing of the first digit stops and [output port
operation] is inhibited.
I If abnormal, the output functions of the host or the
I/O signal cable may be improperly connected.
Shut off power and inspect the I/O cable wiring
and host function again.
(17) Indicate [END] with [UP] and [DOWN] keys. Press
[SET] while [End] is indicated.
The indication mode then returns to the [monitor
mode].
(18) If there is no abnormality during the test run, all wiring
is correct.
Continue to the next step of setting parameters.
D O W N
U P A D J S E T
D O W N
U P A D J S E T
D O W N
U P A D J S E T
ON
OFF
In-position
IN-POS: CN2-33
Attained speed
HI-SPD: CN2-33
Alarm
ALARM: CN2-34
Alarm-A
ALARM: CN2-38
Alarm-B
ALARM: CN2-39
Alarm-C
ALARM: CN2-40
Alarm-D
ALARM: CN2-41