Specifications
Chapter 2 Functions
- 22 -
The reset command should be sent after 300 milliseconds or more from receiving the code “q 0Dh”,
otherwise the [alarm 51: Abnormal encoder signal] may occur.
Reset
Command from the host: ORW+ 00000 0Dh
Response from HA-655: q 0Dh for normal resetting
x 0Dh for abnormal resetting
u Back-up system for absolute data
For protecting the absolute memory against volatilizing while control power is OFF, the absolute encoder
system housed in the FHA-C actuator equips a condenser, and the HA-655 driver provides a battery.
Condenser:
Valid duration: about half hour after control power OFF
(conditions: charged at least 3 hours, at ambient temperature: 25 degree C, no rotation)
Battery:
Lifetime: about one year after control power OFF
(conditions: at ambient temperature: 25 degree C, no rotation)
actual lifetime depends on servicing conditions.
Specifications: lithium battery
model: ER17/33 (3.6V 1600mAh) manufactured by Hitachi Maxell co., Ltd.
Harmonic Drive Systems Inc. is possible to supply the batteries on request.
Exchanging procedures:
When [alarm 56: battery low voltage] occurs, exchange to new battery by the following
procedure:
(1) Shat off all power supply for the HA-655 driver.
(2) Detach a cover of battery case on the front panel of the HA-655 driver.
(3) Pull out the battery from the case by pulling both end of a ribbon.
Note:
“
0
”
means zero.