Specifications

Chapter 6 Setting up parameters
- 119 -
[Test mode]
Analog monitor manual output (speed mode)
Function
It is possible to output voltage signals manually through
the monitor ports in the speed mode. Two analog ports are
provided for monitoring.
Speed monitor: SPD-MON (CN2-23pin)
Current monitor: CUR-MON (CN2-24pin)
Details of display
1st and 2nd digit: [An: analog monitor manual output]
3rd to 6th digit: indicates current output voltage.
Operations
(1) To transfer to in the [analog monitor manual output]
mode, press the [ADJ] key at least 0.1 second.
1st digit [A] flashes now you can output voltage
signals.
(Pressing the [ADJ] key at least 0.1 second again
inhibits the [analog monitor manual output].
(2) To output voltage from [speed monitor: SPD-MON (CN2-23pin)], press the [UP] key.
While pressing, the pin continues to output varying voltage signal.
(3) To output voltage from [current monitor: CUR-MON (CN2-24pin)], press the [DOWN] key.
While pressing, the pin continues to output varying voltage signal.
(4) To terminate [analog monitor manual output] operation, press the [SET] key at least 0.1 second.
Flashing of 1st digit stops and [analog monitor manual output] operation is inhibited.
D O W N
U P A D J S E T
Analog monitor
manual output
Indicates current output voltage
Unit: 0.1V
Range: -10V to +10V
1st digit
6th digit