Technical data

i-KI(R) MTD
24
i-KI(R)_MTD_0031_201110_EN HFC 410A
5. GENERAL TECHNICAL DATA
1 Plant (side) cooling exchanger water (in/out) 23/18 °C
Heat exchanger air (in) 35 °C
2 Plant (side) heating exchanger water (in/out) 30/35 °C
Source (side) heat exchanger air (in) 7 °C 87% R.H.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units
Average sound pressure level, at 1 (m.) distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level
4 Standard configuration
- Not available
i-KIR MTD 0031 RADIANT PANEL APPLICATION
SIZE 0031
COOLING
(1)
Cooling capacity
kW 7,02
Total power input (unit) kW 2,15
EER
ESEER
3,27
-
Heat exchanger water flow m/h 1,21
Heat exchanger pressure drop kPa 49
I-KIR
I-KIR
HEATING
(2)
Heating capacity kW
Total power input (unit) kW
COP
Portata acqua scambiatore m/h
Heat exchanger pressure drop kPa
9,55
2,31
4,13
1,64
35
COMPRESSORS
Numero
Number of circuits N°.
N°. 1
1
Type of regulation
INVERTER
1,5 kg. Oil charge
- kg. Refrigerant charge
R410A Type of refrigerant
% 0-100 Minimum capacity steps
FANS
Numero
Portata aria
N°.
m/s
1
1,00
0,10 kW Singol power input
NOISE LEVELS
(3)
Total sound power dB(A) 64
50 dB(A) Total sound pressure
DIMENSIONS AND WEIGHTS i-KIR outdoor unit
(4)
Length
Larghezza
Altezza
Peso
mm.
mm.
mm.
kg.
850
330
882
85
DIMENSIONS AND WEIGHTS i-EM inside module
Lunghezza
Larghezza
Height
Weight
mm.
mm.
mm.
kg.
(4)
356
109
486
10