Technical data

12. FULL LOAD SOUND LEVEL
i-KI(R) MTD
HFC 410Ai-KI(R)_MTD_0011_0061_201307_EN
38
12. UTILITY WATER CIRCUIT CONNECTION DIAGRAM
Factory connections Installer connections
1
2
11
11
12
12
UTILITY
RETURN
UTILITY
OUTLET
9
8
7
13
3
T
6
13
13
T
6
F
5
4
2
10
1
1
9
1 Pressure gauge
2 Vibration damper joint
3 Shut off valve
4 Calibrating valve
5 Flow switch (obligatory)
6 Thermometer
7 Pump
8 Safety valve
9 Expansion vessel
10 Wire mesh filter
11 Temperature sensor
12 Unit fill/drain valve
13 System vent
SOUND POWER
Octave band [Hz]
Total sound
SIZE 63 125 250 500 1000 2000 4000 8000
level
Sound power level dB(A)
i-KIR 0011m
63 63 60 58 55 51 43 36 60
i-KI 0011m
63 63 60 58 55 51 43 36 60
i-KIR 0031m
64 64 64 62 60 53 50 39 64
i-KI 0031m
64 64 64 62 60 53 50 39 64
i-KIR 0061m
68 67 67 62 60 56 48 40 65
i-KI 0061m
68 67 67 62 60 56 48 40 65
Working conditions
Plant (side) cooling exchanger water (in/out) 12/7 °C
Heat exchanger air (in) 35 °C
Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in com-
pliance with ISO 3744 for non-certified units
Such certification refers specifically to the sound Power Level in dB(A). This is therefore the only acoustic data to be considered as
binding.
SOUND PRESSURE LEVEL
Octave band [Hz] at 1 m
Total sound
SIZE 63 125 250 500 1000 2000 4000 8000
level
Sound pressure level dB(A)
i-KIR 0011m
49 49 46 44 41 37 29 22 46
i-KI 0011m
49 49 46 44 41 37 29 22 46
i-KIR 0031m
50 50 50 48 46 39 36 25 50
i-KI 0031m
50 50 50 48 46 39 36 25 50
i-KIR 0061m
54 53 53 48 46 42 34 26 51
i-KI 0061m
54 53 53 48 46 42 34 26 51
Working conditions
Plant (side) cooling exchanger water (in/out) 12/7 °C
Heat exchanger air (in) 35 °C
Average sound pressure level, at 1 (m.) distance, unit in a free field on a reflective surface; non-binding value obtained from the sound
power level.