Technical data

March 2009
CA08102001E For more information visit: www.eaton.com
33-77
NEMA Contactors & Starters
33
Freedom
Starters — Single-Phase Non-reversing, Full Voltage, Bi-Metallic Overload
Product Description
Single-phase, full voltage magnetic starters connect the
motor directly across the line, allowing it to draw full inrush
current during start-up. These starters are most commonly
used for control of self-starting single-phase motors up to
15 horsepower at 230V. They consist of a 2-pole electromag-
netic contactor to make and break the motor power circuit
and an overload relay to provide running overload protec-
tion. Starters listed in the table include:
■ Two-pole Freedom Series contactor with long life twin
break, silver cadmium oxide contacts. Generously sized
for low resistance and cool operation. Designed to 3 mil-
lion electrical operations at maximum hp and 30 million
mechanical operations to Size 0, 10 million operations to
Size 2 and 6 million operations to Size 3.
■ Three-pole Freedom Series overload with poles 2 and 3
wired in series for motor overload protection. This over-
load is ambient compensated, selectable Manual or Auto-
matic reset, interchangeable Class 10 or 20 heater packs,
1.0 or 1.15 service factor selectability, overload trip indica-
tion and electrically isolated NO-NC contacts (pull RESET
button to test).
■ Holding circuit NO auxiliary contact supplied as standard.
On Size 00, the contact occupies the 4th power pole position.
Sizes 0 – 3 have the NO auxiliary mounted on the right
side of the contactor.
■ Steel mounting plate as standard on all open type starters.
Wired for separate or common control.
Wiring Diagrams
Figure 33-25. Typical Wiring Diagrams — Single-Phase Applications
(Factory Wired)
Product Selection
When Ordering Specify
■ Catalog Number
■ Heater Pack Number (see selection table, Pages 33-107 –
33-108) or full load current.
Table 33-104. Type BN16 NEMA — Manual or Automatic Reset
Overload Relay
Note: Starter Catalog Numbers do not include heater packs. Select 1
carton of 3 heater packs. Heater pack selection, Pages 33-107 –
33-108.
For separate 120V control circuit. For maximum hp at listed motor
voltages, use the rating of other starters of same size.
NEMA Size 1 — Cat. No. BN16DN0AB
NEMA
Size
Maximum Horsepower Magnet
Coil Voltage
(60 Hz)
Open Type 2-Pole
Motor
Voltage
1-Phase Catalog
Number
Price
U.S. $
00 115
230
1/3
1
120
240
BN16AN0AC
BN16AN0BC
0 115
230
1
2
120
240
BN16BN0AC
BN16BN0BC
1 115
230
2
3
120
240
BN16DN0AB
BN16DN0BB
1P 115
230
3
5
120
240
BN16PN0AB
BN16PN0BB
2 115
230
3
7-1/2
120
240
BN16GN0AB
BN16GN0BB
3 115
230
7-1/2
15
120
240
BN16KN0A
BN16KN0B
Accessories . . . . . . . . . . . . . Pages 33-82 – 33-90
Discount Symbol . . . . . . . . . 1CD1
Front View of Panel
1 Phase Motor
When more than
one pushbutton
station is used,
omit Connector “A”
and connect per
sketch at right.
2 Wire Control
Not for Use with
Auto Reset OL Relays
3 Wire Control
START
STOP
AC Lines
1
L1
1
M
OL
A1 A2
2/13
3/14
98
97
96
95
2/T1 4/T2 6/T3
Reset
3
L2
T1
2
T2
4
T1 T2
“C”
3/14
Separate Control
Remove Wire “C” if supplied and connect separate control
lines to the Number 1 Terminal on the remote pilot device
and to the Number 96 Terminal on the overload relay.
1
3/14
2/13
1
START “A”
STOP
START
STOP
3/14
2/13
1