Technical data

CA08102001E For more information visit: www.eaton.com
33-63
NEMA Contactors & Starters
March 2009
33
IT. Manual and Combination Motor Controllers
IT. Manual and Combination Motor Controllers – NEMA Contactors
Accessories
Table 33-87. Line Side Adapters, C320LSA1 and C320LSA2 — When to Use Them for U.S. Applications
SCPD = Short Circuit Protective Device (Circuit Breaker, Fuses).
MMP = Manual Motor Protector.
MMC = Manual Motor Controller.
The C320LSA2 Line Side Adapter is factory assembled on the N309/359.
Reference: Technical Paper AP03402001E.
Note: Line Side Adapters are not required for non-U.S. applications. Most countries outside
of the U.S. classify the MMP as a thermal magnetic circuit breaker.
Table 33-88. Accessories
A308 MMP does not require a Line Side Adapter.
Description Catalog
Number
Price
U.S. $
Line Side Adapter for A307 MMPs
(Required for use with A307 MMPs only
when used as Type E Self-Protected
Manual Combination Starters. Not
required for Group Installation.)
C320LSA1
Line Side Adapter for A309 MMPs
(Required for use with A309 MMPs only
when used as Type E Self-Protected
Manual Combination Starters. Not
required for Group Installation.)
C320LSA2
Wiring Connector Link
(Electrical and mechanical
interconnection between A307 MMP +
IT. 27 mm FVNR/FVR Contactor)
C320WC27
Wiring Connector Link
(Electrical and mechanical
interconnection between A307 MMP +
IT. 45 mm FVNR Contactor)
C320WC45IT
Wiring Connector Link
(Electrical and mechanical
interconnection between A308 MMP +
IT. 54 mm FVNR Contactor)
C320WC54
IT. Manual & Combination Motor Controllers –
NEMA Contactors
Line Side Adapter (LSA)
Not required
Line Side Adapter (LSA)
Not required for any application
Group Installation
Using the in-panel Main
SCPD
and an MMC
without a factory
assembled LSA.
Combination Motor Controller
UL 508 Type F
Combination Motor Controller
—
Only Upstream Feeder SCPD
required with factory
assembled LSA; no dedicated in-panel Main SCPD
for CMC.
Line Side Adapter (LSA)
Required
Types N308/358, (M)N308
Types (M)N307/357 & N309/359
MMP
Only
UL 508 Type E Self-protected
Manual Combination Starter —
Only Upstream Feeder SCPD
required; no dedicated in-panel
Main SCPD
for MMP
Protection in Different
Controller Types
A UL 508 Type E Self-protected Manual
Combination Starter/Motor Controller
consists of a single device having inte-
gral short circuit protection, a main set
of contacts, motor overload protec-
tion, and may also include a UL listed
Line Side Adapter (See Table 33-87).
This type of controller is a legitimate
short circuit protective device and dis-
connect means for the downstream
motor. It does require an upstream
feeder short circuit protective device,
but does not require a dedicated
branch circuit protection or a discon-
nect means if used with a Line Side
Adapter. A UL 508 Type E rating means
that the unit clears a fault and does not
experience any welding of the power
poles. A UL 508 Type E self-protected
manual motor controller will remain
fully functional should a short circuit
within its ratings occur. E.g. A307,
A308 and A309.
An IT. UL 508 Type F Self-protected
Combination Motor Controller consists
of a UL Listed Type E Self-protected
Manual Combination Starter/Motor
Controller, a UL Listed Contactor, and
a UL Listed Line Side Adapter (See
Table 33-87
). While the Type E self-
protected manual motor controller
of this combination motor controller
device is a legitimate short circuit
protective device and disconnect
means for the down-stream motor, the
contactor is not “self-protected.” E.g. IT.
N307 – N309, N357 – N359.
In addition, as a complete assembly
or modular components, the device
should have Type 2 Coordination certi-
fication. Type 2 Coordination means
the Starter or the Controller must
exhibit little or no damage following a
major short circuit fault and should be
able to be returned to proper service
without replacing any parts. E.g. IT.
MMCs, CMCs and MMPs.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD1