Short Circuit Ratings
Table 33-313. Short-Circuit Ratings
Instantaneous adjustable trip.
Circuit breaker.
Inverse time circuit breaker.
Instantaneous adjustable trip with current limiting attachment.
Inverse time with built-in current limiting attachment.
Short-Circuit
Protective
Device
(SCPD)
Max.
Rating
(SCPD)
Circuit
Breaker
Interrupting
Rating
Short-Circuit
Withstand Rating
Typical
Disconnect
Device
Current Voltage
Size 1
Class H Fuse 60A 5,000A 600V 30A DS Sw.
Class J, R
or T Fuse
60A 100,000A
50,000A
480V
600V
30A DS Sw.
65,000A 600V 100A FD-K
Molded Case Sw.
Magnetic
Only
Type CB
3A 100,000A
25,000A
480V
600V
HMCP
HMCPS
7A 100,000A
25,000A
480V
600V
HMCPS
15A 100,000A
25,000A
480V
600V
HMCP
30A 100,000A
25,000A
480V
600V
HMCP
Thermal
Magnetic
Type CB
50A 65,000A
25,000A
65,000A
25,000A
480V
600V
HFD
100,000A
35,000A
100,000A
35,000A
480V
600V
FDC
Magnetic Only
Type CB plus
CL
30A 100,000A 600V HMCP plus CL
Thermal/Mag.
Type CB
plus CL
50A 150,000A 100,000A 600V HFD plus CL
Size 2
Class H Fuse 100A 5,000A 600V 60A DS Sw.
Class J, R
or T Fuse
100A 100,000A
50,000A
480V
600V
60A DS Sw.
65,000A 600V 100A FD-K
Molded Case Sw.
Magnetic
Only
Type CB
50A 100,000A
25,000A
480V
600V
HMCP
Thermal
Magnetic
Type CB
90A 65,000A
25,000A
65,000A
25,000A
480V
600V
HFD
100,000A
35,000A
100,000A
35,000A
480V
600V
FDC
Magnetic Only
Type CB plus
CL
50A 100,000A 600V HMCP plus CL
Thermal/Mag.
Type CB
plus CL
90A 150,000A 100,000A 600V HFD plus CL
Size 3
Class H Fuse 350A 5,000A 600V 100A DS Sw.
Class R Fuse 200A 100,000A
65,000A
480V
600V
100A FD-K
Molded Case Sw.
Class J
or T Fuse
200A 100,000A
65,000A
480V
600V
100A FD-K
Molded Case Sw.
Magnetic
Only
Type CB
200A 100,000A
25,000A
480V
600V
HMCP
Thermal
Magnetic
150A 65,000A
25,000A
65,000A
25,000A
480V
600V
HFD
100,000A
35,000A
100,000A
35,000A
480V
600V
FDC
Magnetic Only
Type CB plus
CL
100A 100,000A 600V HMCP plus CL
Thermal/Mag.
Type CB
plus CL
150A 150,000A 100,000A 600V HFD plus CL
Short-Circuit
Protective
Device
(SCPD)
Max.
Rating
(SCPD)
Circuit
Breaker
Interrupting
Rating
Short-Circuit
Withstand Rating
Typical
Disconnect
Device
Current Voltage
Size 4
Class H Fuse 500A 10,000A 600V 200A DS Sw.
Class J Fuse 400A 100,000A
65,000A
480V
600V
250A JD-K
Molded Case Sw.
Class R or
Class T Fuse
400A 100,000A
65,000A
480V
600V
250A JD-K
Molded Case Sw.
Magnetic
Only
Type CB
150A 100,000A
50,000A
480V
600V
HMCP
Thermal
Magnetic
Type CB
250A 100,000A
35,000A
100,000A
50,000A
480V
600V
JDC
65,000A
25,000A
65,000A
25,000A
480V
600V
HJD
Magnetic Only
Type CB plus
CL
150A 100,000A 600V HMCP plus CL
Size 5
Class H Fuse 600A 10,000A 600V 400A KD-K
Molded Case Sw.
Class J, R
or T Fuse
600A 100,000A 600V
Magnetic
Only
Type CB
250A 100,000A
25,000A
480V
600V
HMCP
400A 100,000A
25,000A
480V
600V
Thermal
Magnetic
Type CB
400A 65,000A
50,000A
35,000A
65,000A
100,000A
25,000A
480V
600V
600V
HFD
KDC
HKD
Size 6
Class J, R
or T Fuse
600A 100,000A
65,000A
480V
600V
600A LD-K
Molded Case Sw.
Class L Fuse 800A 100,000A
65,000A
480V
600V
600A LD-K
Molded Case Sw.
Magnetic
Only
Type CB
600A 100,000A
25,000A
480V
600V
HMCP
800A 65,000A
25,000A
480V
600V
Magnetic Only
HMCP
Thermal
Magnetic
Type CB
600A 65,000A
25,000A
65,000A
35,000A
480V
600V
HLD
800A 50,000A
25,000A
65,000A
25,000A
480V
600V
Thermal Mag-
netic
HMC
Thermal/Mag.
with CL
800A 200,000A 100,000A 600V NB Tri-Pac