Technical data

March 2009
33-200
For more information visit: www.eaton.com CA08102001E
NEMA Contactors & Starters
33
Advantage
Technical Data and Specifications
Table 33-300. Operating Coil Characteristics at Rated Coil Volts, Sizes 1 – 6
Note: The above represent typical production test values and should not be interpreted as a guarantee of actual performance.
Values may vary based upon control power transformer capacities.
Advantage contactors will withstand 110% of their rated
voltage continuously without injury to the operating coils
and will close successfully at 65% of their rated voltage.
Table 33-301. Mechanical Characteristics — Sizes 1 – 6
Also referenced as “kcmil” (1990 NEC).
Motor FLA, Three-Phase AC
Table 33-302. Data from Table 430-150 of 1990 NEC
Note: These current values are for motors running at usual speeds
and with normal torque characteristics. Motors for special low speed
or high torque may require higher current. In all cases, OL trip cur-
rent setting should be selected on basis of information on motor
nameplate or motor card data.
Table 33-303. Temperature Specifications, Sizes 1 – 6
Table 33-304. DIP Switch Overload Protection Settings
Description Size 1 Size 2 Size 3 Size 4 Size 5 Size 6
AC Coil
Burden — Inrush VA
Closed VA
Closed Watts
Pick-Up Volts
Drop-Out Volts
250 VA
25 VA
5W
78V
60V
250 VA
25 VA
5W
78V
60V
500 VA
50 VA
10W
78V
60V
500 VA
50 VA
10W
78V
60V
2600 VA
50 VA
10W
78V
60V
2600 VA
50 VA
10W
78V
60V
Recommended VA rating for machine tool control
power transformers
100 VA 100 VA 150 VA 150 VA 300 VA 300 VA
Description Size 1 Size 2 Size 3 Size 4 Size 5 Size 6
Dimensions in Inches (mm)
Height
Width
Depth
6.50 (165.1)
2.50 (63.5)
4.96 (126.0)
6.50 (165.1)
2.50 (63.5)
4.96 (126.0)
8.00 (203.2)
3.68 (93.5)
6.54 (166.1)
8.00 (203.2)
3.68 (93.5)
6.54 (166.1)
10.08 (256.0)
7.07 (179.6)
7.64 (194.1)
10.08 (256.0)
7.07 (179.6)
7.64 (194.1)
Panel area, square inches
Shipping weight, lbs.
16.25
2.00
16.25
2.00
29.44
6.00
29.44
6.00
71.27
30.00
71.27
30.00
Maximum cable size/phase copper — AWG/MCM
Auxiliary Electrical Circuits Available
Maximum wire size for auxiliary electrical
circuit — AWG
Maximum wire size for control circuit — AWG
8 AWG
8
12
(2) 14
4 AWG
8
12
(2) 14
250 MCM
8
12
(2) 14
250 MCM
8
12
(2) 14
(1) 500 MCM
8
12
(2) 14
(2) 500 MCM
8
12
(2) 14
Mechanical interlock combinations available Vert. Horiz. Vert. Horiz. Vert. Horiz. Vert. Horiz. Vert. Horiz. Vert. Horiz.
Horsepower Squirrel Cage AC
200V 230V 460V 575V
1/4
1/2
3/4
1
1-1/2
1.15
2.3
3.2
4.1
6.0
1
2.0
2.8
3.6
5.2
.6
1.0
1.4
1.8
2.6
.5
.8
1.1
1.4
2.1
2
3
5
7-1/2
10
7.8
11.0
17.5
25.3
32.2
6.8
9.6
15.2
22
28
3.4
4.8
7.6
11
14
2.7
3.9
6.1
9
11
15
20
25
30
40
48.3
62.1
78.2
92
120
42
54
68
80
104
21
27
34
40
52
17
22
27
32
41
50
60
75
100
125
150
177
221
286
359
130
154
192
248
312
65
77
96
124
156
52
62
77
99
125
150
200
414
552
360
480
180
240
144
192
Ambient Temperature
Storage -40° to 100°C
(-40° to 212°F)
Operating -40° to 40°C
(-40° to 104°F)
External (NEMA Enclosed) -40° to 40°C
(-40° to 104°F)
Reset Method Position 8
MANUAL (Non-automatic — wait 5 minutes) 0
AUTOMATIC (Reset time is based on protection Class) 1
Overload Class Position 7 Position 6
10
20
30
None
0
0
1
1
0
1
0
1