Technical data

March 2009
CA08102001E For more information visit: www.eaton.com
33-195
NEMA Contactors & Starters
33
Advantage
Starters — Non-reversing and Reversing
Contents
Description Page
Product Family Overview
Product Description . . . . . . 33-193
Benefits . . . . . . . . . . . . . . . . 33-193
Starters — Non-reversing
and Reversing
Product Description . . . . . . 33-195
Features . . . . . . . . . . . . . . . 33-195
Technical Data . . . . . . . . . . 33-195
Options . . . . . . . . . . . . . . . . 33-195
Product Selection. . . . . . . . 33-196
Technical Data . . . . . . . . . . . . . 33-199
Accessories and Field
Modification Kits . . . . . . . . . 33-204
Renewal Parts . . . . . . . . . . . . 33-206
Control Modules . . . . . . . . . . . 33-207
Dimensions . . . . . . . . . . . . . . . 33-209
Wiring Diagrams . . . . . . . . . . . 33-215
Size 5 and 6 Starter
Product Description
Catalog Number W200 — Non-
reversing Starters (shown above)
Catalog Number W210 — Horizontal
Reversing Starters — long axis
horizontal.
Catalog Number W250 — Vertical
Reversing Starters (not
illustrated) — long axis vertical.
Features
Starter
Small physical size
Brownout protection
Communications capability
Minimized bounce times
Higher contact force
Common auxiliary contacts
Motor Protection
Heaters not required — selectable
settings
Overload protection — accuracy 2%
Phase loss and phase unbalance
protection
Ground current protection
OL Protection Settings
Selectable automatic/manual reset
Selectable trip class — 10, 20, 30 or
no protection (disables overload)
Selectable trip current
Technical Data
Table 33-292. Motor FLA Ranges
For motor full load current (FLA) range of
.47A – 3.81A with a 1.15 to 1.25 service
factor and for motor hp range of 1/4 hp to
2 hp at 460V.
Options
Table 33-293. Optional Features
NEMA
Size
1.15 to 1.25
Service Factor
1.0 Service
Factor
1
1
2
3
4
5
6
.47 – 3.81
3.15 – 27.0
3.15 – 45.0
9.90 – 90.0
9.90 – 135
38.3 – 270
38.3 – 540
.51 – 4.14
3.43 – 27.0
3.43 – 45.0
10.8 – 90.0
10.8 – 135
41.7 – 270
41.7 – 540
Description Catalog
Number
Suffix
Omit Class II Ground-Current
Protection
Y7
Omit Phase-Loss Protection Y4
Omit both Class II Ground-Current
Protection and Phase-Loss
Protection
Y4Y7