Technical data

March 2009
CA08102001E For more information visit: www.eaton.com
33-165
NEMA Contactors & Starters
33
A200
Technical Data and Specifications
Combination Ratings
Table 33-239. Combination Ratings — Sizes 00 – 2
Instantaneous Adjustable Trip.
Circuit Breaker.
Inverse Time Circuit Breaker.
Instantaneous Adjustable Trip with Current Limiting Attachment.
Inverse Time with Built-In Current Limiting Attachment.
Table 33-240. Combination Ratings — Sizes 3 and 4
Instantaneous Adjustable Trip.
Circuit Breaker.
Inverse Time Circuit Breaker.
Instantaneous Adjustable Trip with Current Limiting Attachment.
Inverse Time with Built-In Current Limiting Attachment.
Inverse Time Current Limiting Breaker.
Coil Suffix
Table 33-241. Other Available Coil Voltages — AC and DC Coils
Availability may be limited.
List Price Addition for DC coils.
DC coils for Size 5 and 6 contactors and starters are intermittent duty
rated only. A mechanical latch is required.
DC coils. Use only on contactors originally supplied with a DC coil.
List Price Addition for dual voltage coils.
Short-Circuit
Protective Device
(SCPD)
Max.
Rating
SCPD
Circuit Breaker
Interrupting
Rating
Short-Circuit
Withstand Capability
Current Voltage
Sizes 00, 0, 1
Class H Fuse
Class J Fuse
Class R Fuse
Class T Fuse
60A
60A
60A
60A
5,000A
100,000A
100,000A
100,000A
600V
600V
600V
600V
Magnetic Only
Type CB
30A Marked HMCP 100,000A 480V
50,000A 600V
Thermal/Mag.
Type CB
50A 65,000A 65,000A 480V
25,000A 25,000A 600V
100,000A 100,000A 480V
35,000A 35,000A 600V
Magnetic Only
Type CB + CL
30A HMCP +
Current Limiter
100,000A 600V
Thermal/Mag.
Type CLB
50A 150,000A 100,000A 480V
Size 2
Class H Fuse
Class J Fuse
Class R Fuse
Class T Fuse
100A
100A
100A
100A
5,000A
100,000A
100,000A
100,000A
600V
600V
600V
600V
Magnetic Only
Type CB
50A Marked HMCP 100,000A 480V
50,000A 600V
Thermal/Mag.
Type CB
90A 65,000A 65,000A 480V
25,000A 25,000A 600V
100,000A 100,000A 480V
35,000A 35,000A 600V
Magnetic Only
Type CB + CL
50A HMCP +
Current Limiter
100,000A 600V
Thermal/Mag.
Type CLB
50A 150,000A 100,000A 480V
Short-Circuit
Protective Device
(SCPD)
Max.
Rating
SCPD
Circuit Breaker
Interrupting
Rating
Short-Circuit
Withstand Capability
Current Voltage
Size 3
Class H Fuse
Class J Fuse
Class R Fuse
Class T Fuse
60A
60A
60A
60A
5,000A
100,000A
100,000A
100,000A
600V
600V
600V
600V
Magnetic Only
Type CB
100A Marked HMCP 100,000A 480V
50,000A 600V
Thermal/Mag.
Type CB
150A 65,000A 65,000A 480V
25,000A 25,000A 600V
100,000A 100,000A 480V
35,000A 35,000A 600V
Magnetic Only
Type CB + CL
100A HMCP +
Current Limiter
100,000A 600V
Thermal/Mag.
Type CLB
150A 50,000A 100,000A 480V
Size 4
Class H Fuse
Class J Fuse
Class R Fuse
Class T Fuse
400A
400A
400A
400A
10,000A
100,000A
100,000A
100,000A
600V
600V
600V
600V
Magnetic Only
Type CB
150A Marked HMCP 100,000A 480V
50,000A 600V
Thermal/Mag.
Type CB
250A 65,000A 65,000A 480V
25,000A 25,000A 600V
100,000A 100,000A 480V
35,000A 35,000A 600V
Magnetic Only
Type CB + CL
150A HMCP +
Current Limiter
100,000A 600V
Thermal/Mag.
Type CB + CL
250A 200,000A 100,000A 600V
Thermal/Mag.
Type CLB
250A 150,000A 100,000A 480V
Coils Catalog
Number
Suffix
Coil Rating
(Volts/Hertz)
Catalog
Number
Suffix
Coil Rating
(Volts/Hertz)
AC A
B
C
D
E
G
H
I
J
K
120/60, 110/50
200-208/60
240/60 and 480/60
440/50
600/60 Hz
220/50
380/50
24/60
110-120/50 or
60 Rect. to DC
220-240/50 or
60 Rect. to DC
N
P
R
U
V
W
X
Y
Z
110/50
48/60
120/60 and 240/60
440-480/50 or
60 Rect. to DC
110/60
240/60
480/60
415/50
277/60
DC

L
M
24V DC
48V DC
S
T
125V DC
250V DC
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C