Technical data

March 2009
CA08102001E For more information visit: www.eaton.com
33-109
NEMA Contactors & Starters
33
Freedom
Relays — C396 Electronic Overload
Contents
Description Page
Electronic Overload Relays
Product Description . . . . . . 33-109
Features . . . . . . . . . . . . . . . 33-109
Standards and
Certifications . . . . . . . . . . 33-109
Catalog Number
Selection . . . . . . . . . . . . . 33-110
Product Selection. . . . . . . . 33-111
Accessories. . . . . . . . . . . . . 33-112
Technical Data and
Specifications . . . . . . . . . 33-113
Dimensions. . . . . . . . . . . . . 33-114
Product Description
The C396 is a self-powered, robust
electronic overload designed for inte-
grated use with Freedom NEMA, XT
IEC, and DP contactors. The overload
can also be ordered as a stand-alone
device that is designed for Panel-
Mounting and for use on 35 mm DIN
rail. The C396 has an FLA range of
0.1 – 150 Amps with internal CTs, and
up to 1500 Amps using external CTs.
Features
■ Standard Version: Selectable trip
class (5, 10, 20, 30) with Selectable
Manual or Auto Reset
■ Broad 5:1 FLA range
■ Self-Powered Design, will accept AC
voltages from 12 – 690V 50/60 Hz
■ Ambient Temperature
Compensation
■ Low Heat Generation
■ Phase Loss Protection
■ Phase Unbalance Protection
■ Electrically isolated 1NO-1NC
Contacts (Push-to-Test)
■ Trip Status Indicator
■ FLA range of 0.1 – 1500 Amps
Standards and Certifications
■ UL Listed Components: Stand-
alone, starter-mounted devices and
remote reset kit.
■ CSA Certified Components: Stand-
alone, starter-mounted devices and
remote reset kit.
■ IEC EN 60947-4-1, EN 60947-5-1
■ CE
■ RoHS
C396 Electronic
Overload Relay