Technical data

11. HYDRONIC UNIT
Standard system pump
BWR MTD2
37
HFC 410ABWR_MTD2_0011_0121_201110_EN
Values refer to rated conditions:
Pf (1) Cooling capacity: Source heat exchanger water temperature (in/out) 30/35 °C System heat exchanger water temperature (in/out) 23/18 °C
Pt (2) Heating capacity: Source heat exchanger water temperature (in/out) 0/-3 °C System heat exchanger water temperature (in/out) 30/35 °C
Q (1)(2) System flow-rate
H (1) (2) Available pressure head in system circuit
F.L.I Maximum pump power consumption
Size
Pump
power supply
Pf (1) Q (1) H (1) Pt (2) Q (2) H (2) F.L.I.
Pump
kW m
3
/h kPa kW m
3
/h kPa kW
BWR MTD2 0011ms 230v-50Hz-1Ph 7,10 1,22 54 5,4 0,93 62 0,2 SXM 32-50
BWR MTD2 0025ms 230v-50Hz-1Ph 9,80 1,69 57 7,3 1,26 69 0,21 SXM 32-60
BWR MTD2 0031ms 230v-50Hz-1Ph 12 2,06 81 9,2 1,58 96 0,41 SXM 32-80
BWR MTD2 0041ms 230v-50Hz-1Ph 15,1 2,60 75 11,7 2,01 92 0,41 SXM 32-80
BWR MTD2 0025t 230v-50Hz-1Ph 9,5 1,63 54 7,5 1,29 62 0,21 SXM 32-60
BWR MTD2 0031t 230v-50Hz-1Ph 12 2,06 81 9,1 1,57 96 0,41 SXM 32-80
BWR MTD2 0041t 230v-50Hz-1Ph 15,7 2,70 71 12,2 2,10 89 0,41 SXM 32-80
BWR MTD2 0061t 230v-50Hz-1Ph 21,3 3,66 61 16 2,75 85 0,41 SXM 32-80
BWR MTD2 0071t 230v-50Hz-1Ph 26,9 4,63 116 19,8 3,41 158 0,84 MULTI-H 402
BWR MTD2 0091t 230v-50Hz-1Ph 30,7 5,28 109 23 3,96 151 0,84 MULTI-H 402
BWR MTD2 0101t 230v-50Hz-1Ph 34,8 5,99 141 26,5 4,56 173 1,09 MULTI-H 802
BWR MTD2 0121t 230v-50Hz-1Ph 44,8 7,71 121 33,3 5,73 164 1,09 MULTI-H 802
Standard source pump
Values refer to rated conditions:
Pf (1) Cooling capacity: Source heat exchanger water temperature (in/out) 30/35 °C System heat exchanger water temperature (in/out) 23/18 °C
Pt (2) Heating capacity: Source heat exchanger water temperature (in/out) 0/-3 °C System heat exchanger water temperature (in/out) 30/35 °C
Q (1)(2) Source flow-rate
H (1) (2) Available pressure head in source circuit
F.L.I Maximum pump power consumption
Size
Pump
power supply
Pf (1) Q (1) H (1) Pt (2) Q (2) H (2) F.L.I.
Pump
kW m
3
/h kPa kW m
3
/h kPa kW
BWR MTD2 0011ms 230v-50Hz-1Ph 7,10 1,60 55 5,4 1,30 65 0,21 SXM 32-60
BWR MTD2 0025ms 230v-50Hz-1Ph 9,80 2,10 79 7,3 1,70 92 0,41 SXM 32-80
BWR MTD2 0031ms 230v-50Hz-1Ph 12 2,60 59 9,2 2,20 76 0,41 SXM 32-80
BWR MTD2 0041ms 230v-50Hz-1Ph 15,1 3,30 87 11,7 2,80 122 0,84 MULTI-H 202
BWR MTD2 0025t 230v-50Hz-1Ph 9,5 2,00 82 7,5 1,80 89 0,41 SXM 32-80
BWR MTD2 0031t 230v-50Hz-1Ph 12 2,60 59 9,1 2,20 76 0,41 SXM 32-80
BWR MTD2 0041t 230v-50Hz-1Ph 15,7 3,40 79 12,2 3,00 109 0,84 MULTI-H 202
BWR MTD2 0061t 230v-50Hz-1Ph 21,3 4,50 102 16 3,90 128 0,84 MULTI-H 402
BWR MTD2 0071t 230v-50Hz-1Ph 26,9 5,70 126 19,8 4,80 157 1,09 MULTI-H 802
BWR MTD2 0091t 230v-50Hz-1Ph 30,7 6,60 126 23 5,70 149 1,09 MULTI-H 802
BWR MTD2 0101t 230v-50Hz-1Ph 34,8 7,50 205 26,5 6,50 239 1,51 MULTI-H 803
BWR MTD2 0121t 230v-50Hz-1Ph 44,8 9,60 166 33,3 8,20 213 1,51 MULTI-H 803