Technical data

CAT.201.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog
33-97
January 2001
NEMA Contactors & Starters
33
PowerNet Communication Devices
Advantage Central Monitoring Unit
Vol. 2, Ref. No. [0113]
Contents
Description Page
Central Monitoring Unit . . . . . 33-97
Product Operated Network
Interface (PONI) . . . . . . . . . . 33-99
Central Monitoring Unit
Central Monitoring Unit
Product Description
The Advantage Central Monitoring
Unit is a communications center which
transmits to and receives data from up
to 99 Advantage starters or contactors
or IQ500s equipped with PONI cards.
The CMU can be mounted on the door
of a motor control center or custom
panel using the existing IQ cutout
dimensions.
The eight-digit alphanumeric display
monitors active data, trip data or set
points. The group of data being dis-
played is indicated by one of three
LEDs and is selected by the user. The
two-digit alphanumeric display indi-
cates the address of the device about
which the data is being displayed. This
address is also selected by the user.
Five LEDs are provided which indicate
the present status of the selected
starter. Two additional LEDs are also
provided at the top of the panel, one
which indicates that the CMU is
OPERATIONAL, and another which
indicates ALARM status. An
ACKNOWLEDGE/RESET button
permits the user to reset the CMU
following a device trip.
The CMU can be interfaced into a
larger PowerNet network with the
addition of a PowerNet PONI
Communications Module.
Parameters Displayed
Monitored values:
Device description
1
A
, 1
B
, 1
C
currents
Control voltage (excluding IQ500)
Present time, date
Resettable operation count
Run time, hours
Trip data — same as current values
with cause of trip
Set points:
Device size
OL trip current setting (FLA
setting)
OL trip class
Ground fault protection —
ON/OFF
Phase loss/unbalance protection
— ON/OFF
Reset mode — AUTO/MANUAL
Frequency
Ground fault trip level (IQ500
only)
Ground fault trip delay time
(IQ500 only)
Phase unbalance % (IQ500 only)
IQ500M — Special Functions
Module set points — if LOAD
CONTROL selected:
Load shed level
Load shed delay time
Load resume level
Load resume delay time
Long acceleration time
If UNDERLOAD/JAM selected:
Jam trip level
Jam trip delay time
Jam start delay time
Underload trip level
Underload trip delay time
Underload start delay time
Long acceleration time
Relay control
Technical Data
Device power requirement: 10 VA
maximum
Frequency: 50/60 Hz
Line characteristics: 120 or 240V AC
+20%, -20% (auto selected)
Operating temperature: 0° to 70°C
(32° to 158°F)
Storage temperature: -20° to 85°C
(-4° to 185°F)
Humidity: 0 to 95%, R.H. non-
condensing
Alarm contact ratings —
240V AC: 10A, resistive
30V DC: 10A, resistive
Dimensions
Figure 33-43. Chassis Cutout Dimensions
in Inches (mm)
9.38
(238.3)
4.44
(112.8)
4.44
(112.8)
.25
(6.4)
2.56
(65)
.13
(3.3)
5.12
(130)
5.38
(136.7)
.2 (5.1) Dia.
(6 Holes)
Tab3303.fm Page 97 Monday, October 23, 2000 10:09 PM