Technical data

CAT.201.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog
33-9
January 2001
NEMA Contactors & Starters
33
Starters — 3-Phase, Full Voltage
Freedom Line — Non-reversing and Reversing
Vol. 2, Ref. No. [0025]
Product Selection
When Ordering Supply
Catalog Number
Heater pack number (see selection
table, Pages 33-3633-37 or full load
current.
Table 33-10. Type AN16/AN56 NEMA — Manual or Automatic Reset Overload Relay — Non-reversing and Reversing
Note: Starter Catalog Numbers do not include heater packs. Select one carton of three heater packs. Heater pack selection, Pages 33-3633-37.
1
Maximum horsepower rating of starters for 380V 50 Hz applications:
2
The service-limit current ratings represent the maximum rms current, in amperes, which the controller shall be permitted to carry for protracted periods
in normal service. At service-limit current ratings, temperature rises shall be permitted to exceed those obtained by testing the controller at its
continuous current rating. The current rating of overload relays or trip current of other motor protective devices used shall not exceed the service-limit
current rating of the controller.
3
Common control. For separate 120V control, insert letter D in 7th position of listed Catalog Number. EXAMPLE: AN56VND0CB.
Magnet Coils — AC or DC
Starter coils listed in this section also
have a 50 Hz rating as shown in the
adjacent table. Select required starter
by Catalog Number and replace the
magnet coil alpha designation in the
Catalog Number (_) with the proper
Code Suffix from the adjacent table.
For Sizes 00 – 2 and 5 – 8, the magnet
coil alpha designation will be the next
to last digit of the listed Catalog Num-
ber. EXAMPLE: For a 380V, 50 Hz coil,
change AN16BN0_C to AN16BN0LC.
For all other sizes, the magnet coil
alpha designation will be the last digit
of the listed Catalog Number.
For DC Magnet Coils, see Accessories,
Pages 33-2133-22.
Table 33-11. AC Suffix Code
4
NEMA Sizes 00 and 0 only.
5
NEMA Sizes 00 and 0 only. Sizes 1 – 8 are
24/60 only.
NEMA
Size
Continuous
Ampere
Rating
Service-Limit
Current Rating
2
(Amperes)
Maximum UL Horsepower
1
1-Phase 3-Phase 3-Pole Price
U.S. $
3-Pole Vertical
Reversing
Price
U.S. $
115V 230V 208V 240V 480V 600V Non-reversing Reversing
00 9 11 1/3 1 1-1/2 1-1/2 2 2 AN16AN0_C 182. AN56AN0_C 435.
0 18 21 12 3355AN16BN0_C 228. AN56BN0_C AN56BNV0_ 515.
1 27 32 2 3 7-1/2 7-1/2 10 10 AN16DN0_B 262. AN56DN0_B AN56DNV0_ 585.
2 45 52 3 7-1/2 10 15 25 25 AN16GN0_B 476. AN56GN0_B AN56GNV0_ 1,110.
3 90 104 25 30 50 50 AN16KN0_ 775. AN56KN0_ AN56KNV0_ 1,835.
4 135 156 40 50 100 100 AN16NN0_ 1,760. AN56NN0_ AN56NNV0_ 4,475.
5 270 311 75 100 200 200 AN16SN0_B 4,300. AN56SN0_B 8,590.
6 540 621 150 200 400 400 AN16TN0_C 9,930. AN56TN0_C 19,990.
7 810 932 200 300 600 600 AN16UN0_B 14,160. AN56UN0_B 28,995.
8
3
1215 1400 400 450 900 900 AN16VN0_B 22,010. AN56VN0_B 42,614.
NEMA Size 00 0 12345678
Horsepower 1-1/2 5 10 25 50 75 150 300 600 900
Size 0
Non-reversing Starter
Size 1
Reversing Starter
Size 3 Vertical
Reversing Starter
NEMA Size 0
Cat. No. AN56BN0AC
Coil Volts and Hertz Code Suffix
120/60 or 110/50
240/60 or 220/50
480/60 or 440/50
600/60 or 550/50
A
B
C
D
208/60
277/60
208 – 240/60
4
240/50
E
H
J
K
380 – 415/50
550/50
24/60, 24/50
5
24/50
L
N
T
U
32/50
48/60
48/50
V
W
Y
Technical Data. . . . . . . . . . . . . Pages 33-1233-14
Dimensions . . . . . . . . . . . . . . . Pages 33-2833-30
Special Modifications . . . . . . Page 33-23
Accessories . . . . . . . . . . . . . . . Pages 33-1533-23
Heater Packs . . . . . . . . . . . . . . Pages 33-3633-37
Discount Symbol . . . . . . . . . . . 1CD1
Tab3301.fm Page 9 Monday, October 23, 2000 9:49 PM