Technical data
CAT.201.01.T.E For more information contact Cutler-Hammer at:
www.ch.cutler-hammer.com/catalog
33-75
January 2001
NEMA Contactors & Starters
33
Starters — Non-reversing and Reversing
Advantage Line
Vol. 2, Ref. No. [0091]
Contents
Description Page
Product Family Overview
Product Description . . . . . .
33-73
Benefits . . . . . . . . . . . . . . . .
33-73
Starters — Non-reversing
and Reversing
Product Description . . . . . .
33-75
Features . . . . . . . . . . . . . . .
33-75
Technical Data . . . . . . . . . .
33-75
Options . . . . . . . . . . . . . . . .
33-75
Product Selection. . . . . . . .
33-76
Technical Data
. . . . . . . . . . . . .
33-79
Accessories and Field
Modification Kits
. . . . . . . . .
33-84
Renewal Parts
. . . . . . . . . . . .
33-86
Control Modules
. . . . . . . . . . .
33-87
Dimensions
. . . . . . . . . . . . . . .
33-89
Wiring Diagrams
. . . . . . . . . . .
33-95
Size 5 and 6 Starter
Product Description
Catalog Number W200 — Non-
reversing Starters (shown above)
Catalog Number W210 — Horizontal
Reversing Starters — long axis
horizontal.
Catalog Number W250 — Vertical
Reversing Starters (not
illustrated) — long axis vertical.
Features
Starter
■
Small physical size
■
Brownout protection
■
Communications capability
■
Minimized bounce times
■
Higher contact force
■
Common auxiliary contacts
Motor Protection
■
Heaters not required — selectable
settings
■
Overload protection — accuracy 2%
■
Phase loss and phase unbalance
protection
■
Ground current protection
OL Protection Settings
■
Selectable automatic/manual reset
■
Selectable trip class — 10, 20, 30 or
no protection (disables overload)
■
Selectable trip current
Technical Data
Table 33-118. Motor FLA Ranges
1
For motor full load current (FLA) range of
.47A – 3.81A with a 1.15 to 1.25 service
factor and for motor hp range of 1/4 hp to
2 hp at 460V.
Options
Table 33-119. Optional Features
NEMA
Size
1.15 to 1.25
Service Factor
1.0 Service
Factor
1
1
1
2
3
4
5
6
.47 – 3.81
3.15 – 27.0
3.15 – 45.0
9.90 – 90.0
9.90 – 135
38.3 – 270
38.3 – 540
.51 – 4.14
3.43 – 27.0
3.43 – 45.0
10.8 – 90.0
10.8 – 135
41.7 – 270
41.7 – 540
Description Catalog
Number
Suffix
Omit Class II Ground-Current
Protection
Y7
Omit Phase-Loss Protection
Y4
Omit both Class II Ground-Current
Protection and Phase-Loss
Protection
Y4Y7
Tab3303.fm Page 75 Monday, October 23, 2000 10:09 PM