Technical data

CAT.201.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog
33-7
January 2001
NEMA Contactors & Starters
33
Starters — 3-Phase, Full Voltage
Freedom Line — Non-reversing and Reversing
Vol. 2, Ref. No. [0023]
Contents
Description Page
Product Family Overview
Product Description . . . . . . 33-2
Application Description . . . 33-2
Features . . . . . . . . . . . . . . . 33-2
Standards and
Certifications . . . . . . . . . . 33-3
Starters — 3-Phase Non-reversing
and Reversing, Full Voltage
Product Description . . . . . . 33-7
Features . . . . . . . . . . . . . . . 33-7
Technical Data . . . . . . . . . . 33-8
Wiring Diagrams . . . . . . . . 33-8
Product Selection. . . . . . . . 33-9
Starters — 3-Phase Multispeed
Product Selection. . . . . . . . 33-10
Starters — Single-Phase
Non-reversing, Full Voltage
Product Description . . . . . . 33-11
Wiring Diagrams . . . . . . . . 33-11
Product Selection. . . . . . . . 33-11
Technical Data . . . . . . . . . . . . . 33-12
Accessories . . . . . . . . . . . . . . . 33-15
Auxiliary Contacts . . . . . . . 33-19
DC Magnet Coils . . . . . . . . 33-21
Mounting Plates . . . . . . . . . 33-22
Special Modifications . . . . . . . 33-23
Renewal Parts . . . . . . . . . . . . 33-24
Dimensions . . . . . . . . . . . . . . . 33-26
Product Description
Non-reversing
Three-phase, full voltage magnetic
starters are most commonly used to
switch AC motor loads. Starters con-
sist of a magnetically actuated switch
(contactor) and an overload relay
assembled together.
Reversing
Three-phase, full voltage magnetic
starters are used primarily for revers-
ing of 3-phase squirrel cage motors.
They consist of two contactors and a
single overload relay assembled
together. The contactors are mechani-
cally and electrically interlocked to
prevent line shorts and energization
of both contactors simultaneously.
Features
Bimetallic Ambient Compensated
Overload relays — available in three
basic sizes covering applications up
to 900 hp — reducing number of
different contactor/overload relay
combinations that have to be
stocked.
These overload relays feature:
Selectable Manual or Automatic
Reset operation.
Interchangeable heater packs
adjustable ±24% to match motor
FLA and calibrated for 1.0 and
1.15 service factors. Heater packs
for smaller overload relay will
mount in larger overload relay —
useful in derating applications
such as jogging.
Load lugs built into relay base.
Single-phase protection, Class 20
or Class 10 trip time.
Overload trip indication.
Electrically isolated NO-NC con-
tacts (pull RESET button to test).
Long life twin break, silver cadmium
oxide contacts — provide excellent
conductivity and superior resistance
to welding and arc erosion. Gener-
ously sized for low resistance and
cool operation.
Designed to 3,000,000 electrical
operations at maximum hp ratings
up through 25 hp at 600V.
Steel mounting plate standard on all
open type starters.
Wired for separate or common
control.
Non-reversing
Holding circuit contact(s) supplied
as standard:
Sizes 00 – 3 have a NO auxiliary
contact block mounted on right-
hand side (on Size 00, contact
occupies 4th power pole position
— no increase in width).
Sizes 4 – 5 have a NO contact
block mounted on left side.
Sizes 6 – 7 have a 2NO/2NC
contact block on top left.
Size 8 has a NO/NC contact block
on top left back and a NO on top
right back.
Reversing
Each contactor (Size 00 – 8)
supplied with one NO-NC side
mounted contact block as standard.
NC contacts are wired as electrical
interlocks.
NEMA Size 1 — Cat. No. AN16BN0AB
NEMA Size 1 — Cat. No. AN56DN0AB
Tab3301.fm Page 7 Monday, October 23, 2000 9:49 PM