Technical data

33-38
For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CAT.201.01.T.E
January 2001
NEMA Contactors & Starters
33
Current Sensing Protective Relay
Freedom Line
Vol. 2, Ref. No. [0054]
Contents
Description Page
Current Sensing Protective
Relay
Product Description. . . . . . . 33-38
Features . . . . . . . . . . . . . . . . 33-38
Benefits. . . . . . . . . . . . . . . . . 33-38
Standards and
Certifications . . . . . . . . . . . 33-38
Dimensions . . . . . . . . . . . . . 33-39
Product Selection . . . . . . . . 33-39
Product Description
The IQ500 is a heaterless, current-
sensing, solid-state motor protective
relay with optional communications
capabilities. Several functions are
incorporated into the base relay
(IQ502/IQ504) as standard:
Overload (overcurrent) protection
Phase unbalance and phase loss
protection
Ground current protection (Class II)
The base relay can serve as the initial
building block for a motor protection
system by adding the IQ500M Special
Function Module. The module can
address application related motor load
functions with the additional features:
Underload protection
Long acceleration
Jam protection
Load control
The IQ500 can provide a cost-effective
alternative to conventional protective
relays such as current relays, ground
fault relays and phase loss or phase
unbalance relays. Used with the
PowerNet system, a low-cost, local
area communication network,
information such as current values,
status, setpoint values and cause of
trip can be displayed remotely. The
IQ500 relay is ideal for a variety of
industrial applications such as mining,
timber, material handling, air
conditioning compressors, wastewater
treatment plants and petrochemical
industries.
Features
Overload class is adjustable using
DIP switches for 5, 10, 20 or 30
seconds, maximum trip times at six
times rated current
Designed for 1000V and less
distribution systems
Form C (NO/NC) contact on output
relay
Isolated alarm relay output contact
Communications capability using
IMPACC network
Manual or automatic reset (either a
true manual or remote electrical
reset) — selectable
Overload, Class II ground current,
phase unbalance and single-phase
protection are standard
LED indication (bi-colored — red/
green) for device status, including
overload, phase unbalance or
ground current trip
Special Function Module adds
protection for underload and jam
conditions, also provides for long
acceleration
Optional load control feature avail-
able with special function module
Feed-through current transformer
windows for contactors, NEMA
Sizes 1 – 4 (for Size 5 and larger,
external current transformers can
be used)
Fits mounting footprint of Cutler-
Hammer MORA relay
Panel or starter mountable
Cause of trip is held in memory
through a power loss
Bell alarm contact available for
remote status indication
DIP switch provided for setting
operating frequency — 50 or 60 Hz
Plug-in terminal block for control
power, trip relay and bell alarm
relay connections
Operating temperature: -20° to 60°C
(-4° to 140°F)
Benefits
No external current transformers
are required since they are internal
to the IQ500.
DIP switches used to select func-
tions and settings on base relay are
clearly marked and covered with
screw-on plastic covers.
On the automatic reset, the reset
times can be selected for long
(90 second) or short (10 second)
delay.
Device can be set for different motor
full load currents without additional
parts or modules.
Optional Benefits
With the addition of the IQ500M
Special Function Module, the
enhanced protection includes jam
(overtorque) and underload and
provides long acceleration time
(high inertia load).
The underload and jam protection
functions each have independent
Form C output relays as part of the
module. In addition, the underload
and jam functions each have their
own LEDs for status indication.
The underload and jam functions
also have separate selectable trip
levels and adjustable trip-delay and
start-delay settings.
The IQ500M can be used as a load
control module that allows “shed-
ding and restoring” a particular load
that contributes to the load being
monitored.
The PONI (Product Operated Net-
work Interface) card attaches
directly to the base relay or special
function module for interfacing with
the Cutler-Hammer PowerNet com-
munications system.
Localized display can be achieved
with the Central Monitoring Unit.
Standards and Certifications
UL File No. E19223
Catalog Number IQ502A