NEMA Contactors & Starters
33
Technical Data
A200 Line
Vol. 2, Ref. No. [0147]
Mechanical Characteristics
NEMA Standard ICS 2-110
Direct-current operated contactors
shall withstand 110% of their rated
voltage continuously without injury to
the operating coils and shall close suc-
cessfully at 80% of their rated voltage.
Alternating-current operated contac-
tors shall withstand 110% of their
rated voltage continuously without
injury to the operating coils and shall
close successfully at 85% of their rated
voltage.
Table 33-207. Mechanical Characteristics, Sizes 00 –9
1
For Sizes 5 – 9 contactors only; for starter Sizes 5 – 9, refer to factory.
Table 33-208. Data from Tables 430 — 147 Through 150 of 1996 NEC: Motor Amperes at Full Load
2
, Three-Phase AC
2
These current values are for motors running at usual speeds and with normal torque characteristics. Motors for special low speed or high torque may
require higher current. In all cases, heaters should be selected on basis of information on motor nameplate or motor card data.
Sizes 00, 0, 1 Size 2 Size 3 Size 4 Size 5 Size 6 Size 7 Size 8 Size 9
Dimensions in
Inches (mm)
Height
Width
Depth
6.45
(163.8)
3.31
(84.1)
4.61
(117.1)
7.16
(181.9)
3.31
(84.1)
4.96
(126)
9.93
(252.2)
4.62
(117.3)
6.75
(171.5)
9.93
(252.2)
4.62
(117.3)
6.75
(171.5)
12.00
(304.8)
1
7.00
(177.8)
1
7.75
(196.9)
1
13.50
(342.9)
1
7.00
(177.8)
1
8.75
(222.3)
1
18.62
(472.9)
1
23.50
(596.9)
1
11.00
(279.4)
1
19.25
(489)
1
23.50
(596.9)
1
11.00
(279.4)
1
25.00
(635)
1
32.00
(812.8)
1
13.00
(330.2)
1
Panel Area —
Square Inches
Weight — Pounds
Cable Connection
21.35
3.5 Lbs.
—
23.7
3.5 Lbs.
—
46.0
11.5 Lbs.
—
46.0
11.5 Lbs.
—
84.0
25 Lbs.
Front
94.5
42 Lbs.
Front
437.5
215 Lbs.
Front/Rear
452.4
265 Lbs.
Front/Rear
800
315 Lbs.
Front/Rear
Maximum Cable
Size/Phase Copper
(AWG/MCM)
Auxiliary Electrical
Circuits Available
6 AWG
8
3 AWG
6
1/0
6
4/0
6
1-500 MCM
4
2-500 MCM
4
3-500 MCM
3
4-500 MCM
3
8-500 MCM
4
Latched Version
Available
Yes Yes Yes Yes Yes Yes No No No
Mechanical
Interlock
Combinations
Available
Sizes 00, 0, 1, 2, 3, 4
5
6
7, 8
9
Verti., Horiz.
—
—
—
—
Vert., Horiz.
—
—
—
—
Vert., Horiz.
—
—
—
—
Vert., Horiz.
—
—
—
—
Vert., Horiz.
Vert., Horiz.
Vert., Horiz.
—
—
—
Vert., Horiz.
Vert., Horiz.
Vertical
—
—
—
Vertical
Vertical
Vertical
—
—
Vertical
Vertical
Vertical
—
—
—
Vertical
Vertical
hp Single-Phase
AC
Induction Type Squirrel-Cage
and Wound-Rotor Amperes
DC hp Single-Phase
AC
Induction Type Squirrel-Cage
and Wound-Rotor Amperes
DC
115V 230V 200V 230V 460V 575V 120V 240V 115V 230V 200V 230V 460V 575V 120V 240V
1/6
1/4
1/3
1/2
3/4
4.4
5.8
7.2
9.8
13.8
2.2
2.9
3.6
4.9
6.9
—
—
—
2.5
3.7
—
—
—
2.2
3.2
—
—
—
1.1
1.6
—
—
—
.9
1.3
—
3.1
4.1
5.4
7.6
—
1.6
2.0
2.7
3.8
30
40
50
60
75
—
—
—
—
—
—
—
—
—
—
92
120
150
177
221
80
104
130
154
192
40
52
65
77
96
32
41
52
62
77
—
—
—
—
—
106
140
173
206
255
1
1-1/2
2
3
5
16
20
24
34
56
8
10
12
17
28
4.8
6.9
7.8
11.0
17.5
4.2
6.0
6.8
9.6
15.2
2.1
3.0
3.4
4.8
7.6
1.7
2.4
2.7
3.9
6.1
9.5
13.2
17
25
40
4.7
6.6
8.5
12.2
20
100
125
150
200
250
—
—
—
—
—
—
—
—
—
—
285
359
414
552
—
248
312
360
480
—
124
156
180
240
302
99
125
144
192
242
—
—
—
—
—
341
425
506
675
—
7-1/2
10
15
20
25
80
100
—
—
—
40
50
—
—
—
25.3
32.2
48.3
62.1
78.2
22
28
42
54
68
11
14
21
27
34
9
11
17
22
27
58
76
—
—
—
29
38
55
72
89
300
350
400
450
500
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
361
414
477
515
590
289
336
382
412
472
—
—
—
—
—
—
—
—
—
—
Tab3305.fm Page 131 Monday, October 23, 2000 10:19 PM