Technical data
June 2008
CA08102001E For more information visit: www.eaton.com
37-9
Lighting Contactors
37
Open Control
C30CN Mechanically Held
Operation
3-wire control is the choice for use
with momentary devices allowing
operation from multiple locations. A
momentary pulse of energy operates
the contactor while a second pulse on
an alternate leg returns the contactor
to its original state.
2-wire control is the choice for single
output automatic operation or for
operation from single-pole devices.
When voltage is applied to the input
terminals the contactor is latched into
position (coil is removed from the cir-
cuit while control voltage is continu-
ously supplied). When control voltage
is removed, the latch is disengaged
and the contactor is returned to its
original state.
Instructional Leaflets
50765 C30CN Lighting
Contactor Series
50766 Coil Kit for C30CN
Lighting Contactors
50767 Power Pole Kit for C30CN
Lighting Contactors
50768 Control Module Kit for
C30CN Lighting Contactors
Standards and Certifications
■ UL Listed File E1491, UL Category
Code/Guide NLDX/NLDX7
■ cUL
■ CE
Technical Data and Specifications
Main Power Poles
Table 37-14. Maximum AC Voltage and Amp
Ratings
Table 37-15. Maximum Horsepower Rating
Control Circuit Characteristics
Table 37-16. Coil
Table 37-17. Control Module
Table 37-18. Other Control Module
Characteristics
Auxiliary Contacts Rating:
A600, 24V DC, 24 VA
Ambient Temperature:
-13 to 104°F (-25 to 40°C)
Mounting Position:
Vertical 3-point mounting only.
Wire Size
Table 37-19. Wire Specifications
8 AWG stranded only.
Load Type Amps
Continuous
Poles
1-Phase 3-Phase
Ballast 30 347V AC 600V AC
General Use 30 600V AC 600V AC
Tungsten 20 277V AC 480V AC
AC Resistive 30 600V AC 600V AC
Normal Starting Duty
1 Pole, Single-Phase
Volts Horsepower
110 – 120V
220 – 240V
1
2
3 Poles, Three-Phase
Volts Horsepower
200 – 208V
220 – 240V
440 – 480V
550 – 600V
3
5
10
15
Description VA
Inrush 248 VA
Sealed 28 VA
Input
Voltage
Steady State
Current @ Rated
Voltage (mA)
Maximum
VA
12 – 24V DC 42 2
24V AC 80 5
115 – 120V AC 83 12
200 – 277V AC 91 30
Description Specification
Minimum pulse duration
(3-wire control module)
250 ms
Maximum allowable
leakage current
1.8 mA
EMI 35 V/m
Surge transient peak 6 kV
Frequency Range 40 – 70 Hz
Component Number
of Cables
Wire Range
(Solid or Stranded)
Wire
Temperature
Power Poles 1 14 – 8 AWG 75°C Cu
2 14 – 8 AWG
75°C Cu
Coil 1 or 2 18 – 14 AWG 60°/75°C Cu
Control Module 1 22 – 12 AWG 60°/75°C Cu
Auxiliary Contacts 1 or 2 22 – 12 AWG 60°/75°C Cu