Technical data
June 2008
CA08102001E For more information visit: www.eaton.com
37-17
Lighting Contactors
37
Open Control
A202 Magnetically Latched
60A Size
Product Description
The Cutler-Hammer
®
A202 Lighting
Contactor from Eaton’s electrical busi-
ness provides a safe and convenient
means for local or remote switching of
relatively large tungsten, fluorescent
or mercury arc lamp loads.
Application Description
■ The Magnetically Latched Lighting
Contactors are designed to withstand
the large initial inrush currents of
tungsten lamp loads without contact
welding.
■ The A202 Contactors are fully rated
devices that do not require de-rating
similar to standard motor control
contactors.
■ The Magnetically Latched Lighting
Contactor provides effective control
in applications such as office build-
ings, industrial plants, hospitals,
stadiums, airports, etc.
Features
■ Designed and tested specifically for
lighting and resistive loads
■ Easy to install and maintain
■ No control power necessary to
maintain contact closure
Operation
A permanent magnet is built into the
contactor structure that will maintain
the contactor in its energized state
indefinitely without using control
power. When energized, a DC current is
applied to the latch coil, producing a
magnetic field that reinforces the polar-
ity of the permanent magnet, pulling in
the contactor. The coil clearing interlock
disconnects the current to the coil. In
order to drop out the contactor, it is
necessary to apply a field through the
STOP coil in the reverse direction to the
permanent magnet. This momentarily
cancels the magnetic attraction and the
contactor drops out.
Instructional Leaflets
IL16965 30A (2, 3, 4, 5 Poles)
IL16966 60 – 200A (2, 3, 4, 5 Poles)
Standards and Certifications
■ UL Listed File # E44424, Guide NRNT
■ CSA Certified File # LR39402,
Class 3231-01
Technical Data and
Specifications
■ Terminals
❑ All except 30A devices: Cu/Al
❑ 30A devices: Cu only
■ Ballast load: 600 AC, breaking all
lines
■ Tungsten lamp loads, maximum
volts
❑ Line-to-line: 480V AC
❑ Line-to-neutral: 277V AC
Accessories
See A200 NEMA Contactor Accessories,
Page 33-166 – 33-168.
Wiring Diagrams
Figure 37-8. Standard Wiring
Figure 37-9. Two-Wire Control
Red3
2
Red
Red
AC
AC
OFF
(+)
Control Line
Auxiliary
Contact
(Option)
Typical
Control
Station
Line
Load
Close
Close
Open
Open
ON
Black
White
(+)
L2
(+)
(–)
Standard Wiring
The standard wiring of an A202 con-
tactor can be controlled by a separate
customer supplied
single-pole double-
throw controlling station.
Red3
2
Red
Red
AC
AC
OFF
CM
CM
CM
(+)
Line
or
Neutral
Line
Switch
Auxiliary
Contact
(Option)
CM
Control
Line
Load
ON
Black
White
(+)
L2
(+)
(–)
Two-Wire Control
Two-wire control can be accom-
plished with a customer supplied
relay with 1NO/1NC auxiliary
contacts, wire as shown.