Specifications

TECHNICAL SPECIFICATIONS RENOVENT HR SWB
Technical Specifications Renovent HR SWB
Dimension duct connection [mm] Ø 150
Weight [ kg] 35
Supply voltage [V~Hz] 230/50
Protection degree IP31
Temperature efficiency [%] 95
Mode Absence Presence Cooking/showering Maximum
mode mode mode mode
Ventilation capacity [m
3
/h] 100 150 225 300
Resistance ducts system [Pa] 20 44 100 175
Rated power [W] 18 30 74 146
EPS calculation
Brink Climate Systems has information available for correctly entering data in an EPS calculation. Please contact our Consultancy
Department.
Acoustic data Absence Presence Cooking/showering
mode mode mode
Static pressure [Pa] 40 80 160
Acoustic capacity housing emission [dB(A)] 38 46 55
Acoustic capacity duct “from" dwelling [dB(A)] 36 46 55
Acoustic capacity duct “to" dwelling [dB(A)] 56 66 75
SOUND CAPACITY LEVEL L
W
RENOVENT HR SWB
FAN GRAPH RENOVENT HR SWB
GOSB
0
25
50
75
100
125
150
175
200
225
250
275
300
325
350
375
400
80
57
33
42
11
20
7
47
73
15
28
37
39
61
13
24
32
8
48
64
111
36
Resistance ducts system [Pa]
3
/h]
= Power per fan [W]
15
The above acoustic data is based on the unit only and is not related to the level within the room. External noise being transmitted from outside into the dwelling is greatly reduced in ‘airtight’
construction – as a result background noises are more noticeable. The Climate OK system incorporates acoustic measures as standard procedure. Such as, decoupling, insulation and acoustically
treated manifolds. In addition, design criteria dictates velocities of around 2,5m/s in the tributary ducts. A Climate OK installation has a targeted system noise level of +/- 29,5dB(A). This figure can
be further reduced with additional acoustic treatment if specified.