SUPERSERVER 6026TT-HT(R)F/HIBX(R)F/HIBQ(R)F USER'S MANUAL
Power Supply Failure: Redundant Power (Two Modules)
The SuperServer 6026TT-HTRF, 6026TT-HIBXRF and 6026TT-HIBQRF servers
have two 1400 Watt power supply modules to provide redundant power for the
system. If either of the two power supply modules fail, the other module will take
the full load and allow the system to continue operation without interruption. The
LED on the control panel will fl ash slowly (about 4 seconds on and 4 off) and remain
fl ashing until the failed unit has been replaced. Replacement units can be ordered
directly from Supermicro (see contact information in the Preface). The power supply
units have a hot-swap capability, meaning you can replace the failed unit without
powering down the system.
Removing/Replacing the Power Supply (Figure 6-8)
1. Disconnect the AC power cord from the failed module.
2. Push the colored release tab to the side and pull the power module out with
the handle provided.
3. Replace the failed power supply module with the exact same model from
Supermicro.
4. Carefully insert the new module into position in the chassis and push it in until
fully seated. You should see the LED on the rear of the module turn amber
showing that power (from the backup module) is present.
5. Reconnect the AC power cord to the new module.