Power cabling: 32A at 380-415V 3-phase (international)
As shown in Figure 5-7, one 3-phase 32A wye PDU (WW) can provide power
feeds for two chassis. In this case, an appropriate 3-phase power cable is
selected for the Ultra-Dense Enterprise PDU+, which then splits the phases,
supplying one phase to each of the three PSUs within each chassis. One
3-phase 32A wye PDU can power two fully populated chassis within a rack. A
second PDU may be added for power redundancy from an alternative power
source, if the chassis is configured N+N.
Figure 5-7 shows a typical configuration with a 32A 3-phase wye supply at
380-415 VAC (often termed “WW” or “International”) N+N.
Figure 5-7 Example power cabling 32A at 380-415V 3-phase (international)
The maximum number of Enterprise Chassis that may be installed with a 42 U
rack is four, so this configuration requires a total of four 32A 3-phase wye feeds
into the rack, to provide for a fully redundant N+N configuration.
IEC320 16A C19-C20
3m power cable
40K9611 IBM DPI 32a
Cord (IEC 309 3P+N+G)
46M4002 1U 9
C19/3 C13 Switched and
monitored DPI PDU
L1
L2
L3
G
N
L1
L2
L3
G
N
= Power
cables